6EP1353-0AA00
SITOP DUAL 2X 15 V/3.5 A

From SIEMENS

SITOP DUAL 2X 15 V/3.5 A
SITOP power 15 V dual output Stabilized power supply input: 120-230 V AC output: 2X 15 V DC/3.5 A
Input
Input1-phase AC
Rated voltage value Vin rated120 ... 230 V
Voltage range AC93 ... 264 V
Wide-range inputYes
Overvoltage resistanceSurge voltage in accordance with EN 61000-6-2 Table 4
Mains buffering at Iout rated, min.10 ms; at Vin = 120 V, 40 ms at Vin = 187 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 120 V1.9 A
at rated input voltage 230 V1.15 A
Switch-on current limiting (+25 °C), max.30 A
Duration of inrush current limiting at 25 °C
typical3 ms
I²t, max.3 A²·s
Built-in incoming fuseT 4 A/250 V (not accessible)
Protection in the mains power input (IEC 898)Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC15 V
Output voltage2 x 15 V DC
at output 1 at DC Rated value15 V
at output 2 at DC Rated value15 V
Total tolerance, static ±2 %
Static mains compensation, approx.0.2 %
Static load balancing, approx.0.2 %
Residual ripple peak-peak, max.50 mV
Residual ripple peak-peak, typ.20 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)150 mV
Adjustment range14.5 ... 17 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer
Status displayGreen LED grün for Vout >10 V (summation display)
Signaling-
On/off behaviorOvershoot of Vout < 3 %
Startup delay, max.1 s
Rated current value Iout rated3.5 A
Output current
at output 1 Rated value3.5 A
at output 2 Rated value3.5 A
Current range0 ... 3.5 A
Note+45 ... +60 °C: Derating 2%/K
Supplied active power typical105 W
Parallel switching for enhanced performanceYes
Numbers of parallel switchable units for enhanced performance2
Efficiency
Efficiency at Vout rated, Iout rated, approx.80 %
Power loss at Vout rated, Iout rated, approx.27 W
Protection and monitoring
Output overvoltage protectionYes, according to EN 60950-1
Current limitation4.9 A
Current limitationLimit point < 4.9 A; switch-off point < 6 A
Property of the output Short-circuit proofYes
Short-circuit protectionElectronic shutdown, automatic restart
Overload/short-circuit indicator-
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra low output voltage Vout according to EN 60950-1
Protection classClass I
Leakage current
maximum3.5 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 142), File E179336
Explosion protection-
FM approval-
CB approvalNo
Marine approval-
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55011 Class A
Supply harmonics limitation-
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation0 ... 60 °C
— Notewith natural convection
during transport-40 ... +70 °C
during storage-40 ... +70 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL1, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
OutputP15_1, GND_1, GND_2: 1 screw terminal each for 0.5 ... 2.5 mm²; P15_2: 2 screw terminals for 0.5 ... 2.5 mm²
Auxiliary-
Width of the enclosure75 mm
Height of the enclosure125 mm
Depth of the enclosure125 mm
Required spacing
top100 mm
bottom100 mm
left0 mm
right0 mm
Weight, approx.0.75 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links