6EP1336-3BA10
SITOP PSU8200 24 V/20 A

From SIEMENS

SITOP PSU8200 24 V/20 A
SITOP PSU8200 20 A Stabilized power supply input: 120-230 V AC 110-220 V DC output: 24 V DC/20 A
Input
Input1-phase AC or DC
Rated voltage value Vin rated120 ... 230 V
Voltage range AC85 ... 275 V
NoteDerating of temperature necessary down to 50 °C at Vin < 100 V AC or DC
Supply voltage
at DC110 ... 220 V
Input voltage
at DC88 ... 350 V
Wide-range inputYes
Mains buffering at Iout rated, min.20 ms; at Vin = 230 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range45 ... 65 Hz
Input current
at rated input voltage 120 V4.6 A
at rated input voltage 230 V2.5 A
Switch-on current limiting (+25 °C), max.20 A
I²t, max.5 A²·s
Built-in incoming fuseYes
Protection in the mains power input (IEC 898)Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.1 %
Static load balancing, approx.0.3 %
Residual ripple peak-peak, max.100 mV
Residual ripple peak-peak, typ.80 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)200 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)100 mV
Adjustment range24 ... 28.8 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer
Status displayGreen LED for 24 V OK
SignalingRelay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behaviorNo overshoot of Vout (soft start)
Startup delay, max.1.5 s
Voltage rise, typ.50 ms
Rated current value Iout rated20 A
Current range0 ... 20 A
Note+60 ... +70 °C: Derating 3%/K
Supplied active power typical480 W
Short-term overload current
at short-circuit during operation typical60 A
Duration of overloading capability for excess current
at short-circuit during operation25 ms
Constant overload current
on short-circuiting during the start-up typical30 A
Parallel switching for enhanced performanceYes; switchable characteristic
Numbers of parallel switchable units for enhanced performance2
Efficiency
Efficiency at Vout rated, Iout rated, approx.93 %
Power loss at Vout rated, Iout rated, approx.42 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.5 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.1 %
Load step setting time 50 to 100%, typ.1 ms
Load step setting time 100 to 50%, typ.1 ms
Setting time maximum5 ms
Protection and monitoring
Output overvoltage protection< 33 V
Current limitation, typ.21.5 A
Property of the output Short-circuit proofYes
Short-circuit protectionAlternatively, constant current characteristic approx. 23 A or latching shutdown
Enduring short circuit current RMS value
typical23 A
Overcurrent overload capability in normal operationoverload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicatorLED yellow for "overload", LED red for "latching shutdown"
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection classClass I
Leakage current
maximum3.5 mA
typical1 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protectionIECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3
FM approval-
CB approvalYes
Marine approvalABS, DNV GL
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-25 ... +70 °C
— NoteWith natural convection; startup tested starting from -40 °C nominal voltage
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded
Output+, -: 2 screw terminals each for 0.2 ... 4 mm²
Auxiliary13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²
Width of the enclosure90 mm
Height of the enclosure125 mm
Depth of the enclosure125 mm
Required spacing
top50 mm
bottom50 mm
left0 mm
right0 mm
Weight, approx.1.2 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15
Electrical accessoriesBuffer module
Mechanical accessoriesDevice identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C667 048 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links