6EP1332-2BA10
SITOP SMART 24 V/2.5 A

From SIEMENS

SITOP SMART 24 V/2.5 A
SITOP smart 60 W Stabilized power supply input: 120/230 V AC, output: DC 24 V/2,5 A
Input
Input1-phase AC
NoteSet by means of selector switch on the device
Supply voltage
1 at AC Rated value120 V
2 at AC Rated value230 V
Input voltage
1 at AC85 ... 132 V
2 at AC170 ... 264 V
Wide-range inputNo
Overvoltage resistance2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.20 ms; at Vin = 93/187 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 120 V1.1 A
at rated input voltage 230 V0.65 A
Switch-on current limiting (+25 °C), max.27 A
Duration of inrush current limiting at 25 °C
typical3 ms
I²t, max.0.3 A²·s
Built-in incoming fuseT 2 A/250 V (not accessible)
Protection in the mains power input (IEC 898)Recommended miniature circuit breaker: from 3 A characteristic C
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.1 %
Static load balancing, approx.0.5 %
Residual ripple peak-peak, max.150 mV
Residual ripple peak-peak, typ.10 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)50 mV
Adjustment range22.8 ... 28 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer
Status displayGreen LED for 24 V OK
On/off behaviorOvershoot of Vout approx. 4 %
Startup delay, max.0.1 s
Voltage rise, typ.50 ms
Rated current value Iout rated2.5 A
Current range0 ... 3 A
Note3 A up to +45 °C
Supplied active power typical60 W
Short-term overload current
on short-circuiting during the start-up typical7 A
at short-circuit during operation typical7 A
Duration of overloading capability for excess current
on short-circuiting during the start-up100 ms
at short-circuit during operation200 ms
Parallel switching for enhanced performanceYes
Numbers of parallel switchable units for enhanced performance2
Efficiency
Efficiency at Vout rated, Iout rated, approx.85 %
Power loss at Vout rated, Iout rated, approx.9 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.3 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.1 %
Load step setting time 50 to 100%, typ.0.2 ms
Load step setting time 100 to 50%, typ.0.2 ms
Protection and monitoring
Output overvoltage protection< 33 V
Current limitation3.2 ... 3.4 A
Property of the output Short-circuit proofYes
Short-circuit protectionConstant current characteristic
Enduring short circuit current RMS value
typical5 A
Overload/short-circuit indicator-
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection classClass I
Leakage current
maximum3.5 mA
typical0.4 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, cCSAus (CSA C22.2 No. 60950-1, UL 60950-1, UL 1604)
Explosion protectionATEX (EX) II 3G Ex nA II T4; UL 1604 Class I, Div. 2, Group ABCD
FM approval-
CB approvalYes
Marine approvalABS, GL
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationnot applicable
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation0 ... 60 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
OutputL+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
Auxiliary-
Width of the enclosure32.5 mm
Height of the enclosure125 mm
Depth of the enclosure125 mm
Required spacing
top50 mm
bottom50 mm
left0 mm
right0 mm
Weight, approx.0.32 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C2 154 801 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links