| SIMATIC ET 200SP HA, analog HART input module, AI 16XI 2-wire HART HA, suitable for terminal block H1, M1, color code CC01, channel diagnostics, 16-bit, +/-0.1%, |
General information |
Product type designation | AI 16 x I 2-wire mA HART |
Firmware version | V1.0 |
FW update possible | Yes |
Usable terminal block | TB type H1, M1 and N0 |
Color code for module-specific color identification plate | CC01 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
PCS 7 configurable/integrated as of version | V9.0 |
Redundancy |
Redundancy capability | Yes; With TB type M1 |
CiR – Configuration in RUN |
Reparameterization possible in RUN | Yes |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption (rated value) | 80 mA; without sensor supply |
Current consumption, max. | 90 mA; without sensor supply |
Encoder supply |
24 V encoder supply |
24 V | Yes |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.5 A) |
Output current per channel, max. | 0.5 A |
Output current per module, max. | 2 A |
Power loss |
Power loss, typ. | 4.5 W; without sensor supply |
Address area |
Address space per module |
Address space per module, max. | 34 byte; 32-byte inputs and 2 bytes for QI information |
Address space per module with HART, max. | 74 byte; 32-byte inputs and 2 bytes for QI information, 40-byte inputs for HART |
Address space per module with MultiHART, max. | 41 byte; 32-byte inputs for HART and 2 bytes for QI information, 6-byte inputs for HART, and 1-byte output for MultiHART command |
Analog inputs |
Number of analog inputs | 16 |
permissible input current for current input (destruction limit), max. | 30 mA |
Input ranges (rated values), currents |
0 to 20 mA | Yes; 16 bit incl. sign |
Input resistance (0 to 20 mA) | 250 Ω |
4 mA to 20 mA | Yes; 16 bit incl. sign |
Input resistance (4 mA to 20 mA) | 250 Ω |
Cable length |
shielded, max. | 800 m; Shielded |
Analog value generation for the inputs |
Measurement principle | integrating (Sigma-Delta) |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; 15 bit at 0 ... 10 mA and 60 Hz interference suppression |
Integration time, parameterizable | Yes; channel by channel |
Smoothing of measured values |
parameterizable | Yes; none, weak, medium, strong, channel-by-channel |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.005 %/K |
Crosstalk between the inputs, min. | 60 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 0.5 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.1 % |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Alarms |
Diagnostic alarm | Yes |
Limit value alarm | Yes; two upper and two lower limit values in each case |
Diagnostic messages |
Monitoring the supply voltage | Yes |
Wire-break | Yes; channel by channel |
Short-circuit | Yes; Channel-by-channel, short-circuit of the encoder supply to ground or of an input to the encoder supply |
Overflow/underflow | Yes; channel by channel |
Diagnostics indication LED |
MAINT LED | Yes; yellow LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | Yes; Green LED |
for channel diagnostics | Yes; Red LED |
for module diagnostics | Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | No |
Isolation |
Isolation tested with | 1 500 V DC/1 min, type test |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | -40 °C |
horizontal installation, max. | 70 °C; Observe derating |
vertical installation, min. | -40 °C |
vertical installation, max. | 60 °C; Observe derating |
Dimensions |
Width | 22.5 mm |
Height | 115 mm |
Depth | 138 mm |
Weights |
Weight, approx. | 148 g |
last modified: | 03/13/2019 |