| SIMATIC ET 200SP HA, configurable I/O module, AI-DI16/DQ16X24VDC HART, suitable for terminal block H1, M1, color code CC00, channel diagnostics, 16-bit, +/-0.1%, |
General information |
Product type designation | AI-DI 16/DQ 16x24VDC HART HA |
Firmware version | V1.0 |
FW update possible | Yes |
Usable terminal block | TB type H1, M1 and N0 |
Color code for module-specific color identification plate | CC00 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
PCS 7 configurable/integrated as of version | V9.0 |
Operating mode |
DI | Yes |
Counter | No |
DQ | Yes |
DQ with energy-saving function | No |
PWM | No |
Oversampling | No |
MSI | No |
MSO | No |
Redundancy |
Redundancy capability | Yes; With TB type M1 |
CiR – Configuration in RUN |
Reparameterization possible in RUN | Yes |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption (rated value) | 80 mA; without sensor supply |
Current consumption, max. | 90 mA; without sensor supply |
Encoder supply |
Number of outputs | 16 |
Output voltage encoder supply, min. | 18.2 V |
Short-circuit protection | Yes; per channel, electronic |
24 V encoder supply |
24 V | Yes |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.5 A) |
Output current per channel, max. | 0.5 A |
Output current per module, max. | 2 A |
Power loss |
Power loss, typ. | 4.5 W; without sensor supply |
Address area |
Address space per module |
Address space per module, max. | 42 byte; Address space per module (analog): 42 bytes. Of which 34 bytes for outputs, 2 bytes for outputs and 6 bytes for QI information. Address space per module (digital): 26 bytes. Of which 2 bytes for inputs, 2 bytes for outputs, 18 bytes for SoE, and 4 bytes for QI information |
Address space per module with HART, max. | 82 byte; 34-byte inputs, 2-byte outputs, 40 bytes for HART secondary variables, and 6 bytes for QI information |
Address space per module with MultiHART, max. | 70 byte; 34-byte inputs, 2-byte outputs, 24-byte HART inputs, 4-byte HART outputs, and 6 bytes for QI information |
Digital inputs |
Number of digital inputs | 16 |
Digital inputs, parameterizable | Yes |
Source/sink input | Yes; P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input characteristic curve in accordance with IEC 61131, type 2 | No |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Pulse extension | Yes; Off, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s |
Time stamping | Yes; Resolution 10 ms |
Time stamp (with precision of 1 ms) | Yes; Resolution 1ms |
Edge evaluation | Yes; rising edge, falling edge, edge change |
Input voltage |
Type of input voltage | DC |
Rated value (DC) | 24 V |
for signal "0" | -30 to +5V |
for signal "1" | +11 to +30V |
Input current |
for signal "1", typ. | 2.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Digital outputs |
Number of digital outputs | 16 |
Current-sinking | No |
Current-sourcing | Yes |
Short-circuit protection | Yes; Response threshold 0.7 A to 1.3 A |
Open-circuit detection | Yes |
Overload protection | Yes |
Limitation of inductive shutdown voltage to | L+ -(37 to 41V) |
Controlling a digital input | Yes |
Switching capacity of the outputs |
with resistive load, max. | 0.5 A |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 48 Ω |
upper limit | 12 kΩ |
Output current |
for signal "1" rated value | 0.5 A |
for signal "0" residual current, max. | 0.7 mA |
Output delay with resistive load |
"0" to "1", typ. | 50 µs |
"1" to "0", typ. | 100 µs |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 2 Hz |
on lamp load, max. | 10 Hz |
Total current of the outputs |
Current per channel, max. | 0.5 A |
Current per module, max. | 2 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Analog inputs |
Number of analog inputs | 16 |
permissible input current for current input (destruction limit), max. | 30 mA |
Input ranges (rated values), currents |
0 to 20 mA | Yes; 16 bit incl. sign |
Input resistance (0 to 20 mA) | 250 Ω |
4 mA to 20 mA | Yes; 16 bit incl. sign |
Input resistance (4 mA to 20 mA) | 250 Ω |
Analog value generation for the inputs |
Measurement principle | integrating (Sigma-Delta) |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; 15 bit at 0 ... 10 mA and 60 Hz interference suppression |
Integration time, parameterizable | Yes; channel by channel |
Smoothing of measured values |
parameterizable | Yes; none, weak, medium, strong, channel-by-channel |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | Yes |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.005 %/K |
Crosstalk between the inputs, min. | 60 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 0.5 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.1 % |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms |
Diagnostic alarm | Yes |
Limit value alarm | Yes; two upper and two lower limit values in each case |
Diagnostic messages |
Monitoring the supply voltage | Yes |
Wire-break | Yes; channel by channel |
Short-circuit to M | Yes; Encoder supply to M, channel by channel |
Group error | Yes |
Overflow/underflow | Yes; channel by channel |
Diagnostics indication LED |
MAINT LED | Yes; yellow LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | No |
for channel diagnostics | No |
for module diagnostics | Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | No |
Isolation |
Isolation tested with | 1 500 V DC/1 min, type test |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | -40 °C |
horizontal installation, max. | 70 °C; Observe derating |
vertical installation, min. | -40 °C |
vertical installation, max. | 60 °C; Observe derating |
Dimensions |
Width | 22.5 mm |
Height | 115 mm |
Depth | 138 mm |
Weights |
Weight, approx. | 150 g |
last modified: | 03/02/2019 |