| SIMATIC IPC477E PRO fully enclosed IP65; 4USB (back); w/o USB (front); Ethernet (10/100/1000); |
Installation type/mounting |
Mounting | For mounting on stand or supporting bracket |
Design | Panel PC on pedestal or supporting arm |
maximum permissible installation angle +/- | ±45 ° |
Supply voltage |
Type of supply voltage | 24 V DC |
Line frequency |
Rated value 50 Hz | Yes |
Rated value 60 Hz | Yes |
Processor |
Processor type | Celeron G3902 (2C/2T, 1.6 GHz, 2 MB Cache); Core i3-6102E (2C/4T, 1.9 GHz, 3 MB Cache); Core i5-6442EQ (4C/4T, 1.9 (2.7) GHz, 6 MB Cache, iAMT); Xeon E3-1505L v5 (4C/8T, 2.0 (2.8) GHz, 8 MB Cache, iAMT) |
Graphic |
Graphics controller | Intel HD graphics controller |
Drives |
Optical drives | possible as external drive via USB |
SSD | Yes; 1x 128 GB, 1x 240 GB SSD, 1x 480 GB SSD |
Memory |
Type of memory | DDR4 SO-DIMM |
Main memory | 4 GB to 16 GB, ECC optional |
Capacity of main memory, max. | 16 Gbyte |
Data areas and their retentivity |
Retentive data area (incl. timers, counters, flags), max. | 512 kbyte; 128 KB can be stored in the buffer time |
Hardware configuration |
Slots |
Number of PCI slots | 0; Different to the built-in unit |
Number of PCI slots | 0; Different to the built-in unit |
Number of compact flash slots | 1; CFast |
Interfaces |
Number of industrial Ethernet interfaces | 3; 3x Ethernet (RJ45) |
USB port | 4x USB 3.0 onboard (rear) |
Connection for keyboard/mouse | USB / USB |
serial interface | Without / 2x COM (RS 232 / 422 / 485), selectable in the BIOS |
Video interfaces |
Graphics interface | 2x DisplayPort |
Industrial Ethernet |
Industrial Ethernet interface | 3x Ethernet (RJ45) |
— 100 Mbps | Yes |
— 1000 Mbps | Yes |
Interrupts/diagnostics/status information |
Bus diagnostics | Yes |
Integrated Functions |
Monitoring functions |
Temperature monitoring | Yes |
Watchdog | Yes |
Fan | No |
Monitoring function via network | Optional |
EMC |
Interference immunity against discharge of static electricity |
Interference immunity against discharge of static electricity | ±6 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC 61000-4-2 |
Interference immunity against high-frequency electromagnetic fields |
Interference immunity against high frequency radiation | 10 V/m, 80 ... 2 000 MHz, 80 % AM acc. to IEC 61000-4-3; 3 V/m, 2 ... 2.7 GHz; 10 V, 10 kHz ... 80 MHz acc. to IEC 61000-4-6 |
Interference immunity to cable-borne interference |
Interference immunity on supply cables | ±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5, surge symmetric; ±2 kV acc. to IEC 61000-4-5, surge asymmetric |
Interference immunity on signal cables >30m | ±2 kV acc. to IEC 61000-4-5, surge, length > 30 m |
Interference immunity on signal cables < 30m | ±1 kV acc. to IEC 61000-4-4; burst; length < 3 m; ±2 kV acc. to IEC 61000-4-4; burst; length > 3 m |
Interference immunity against voltage surge |
asymmetric interference | ±2 kV acc. to IEC 61000-4-5, surge asymmetric |
symmetric interference | ±1 kV acc. to IEC 61000-4-5, surge symmetric |
Interference immunity to magnetic fields |
Interference immunity to magnetic fields at 50 Hz | 100 A/m; to IEC 61000-4-8 |
Emission of conducted and non-conducted interference |
Interference emission via line/AC current cables | EN 61000-6-3, EN 61000-6-4, CISPR 22 Class B, FCC Class A |
Degree and class of protection |
IP65 (all-round) | Yes; IP65 fully enclosed |
IP (at the front) | IP65 |
IP (rear) | IP65 |
Standards, approvals, certificates |
CE mark | Yes; CE marking / EC Declaration of Conformity |
UL approval | Yes |
UL 508 | Yes |
cULus | Yes |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | No |
EMC | CE, EN 61000-6-4; CISPR 22 Class A; FCC Class A |
Marine approval |
Germanischer Lloyd (GL) | Yes |
American Bureau of Shipping (ABS) | Yes |
Det Norske Veritas (DNV) | Yes |
Korean Register of Shipping (KRS) | Yes |
Lloyds Register of Shipping (LRS) | Yes |
Ambient conditions |
Ambient temperature during operation |
Ambient temperature during operation | 5 to +45°C |
Ambient temperature during storage/transportation |
min. | -20 °C |
max. | 60 °C |
Relative humidity |
Relative humidity | Tested according to IEC 60068-2-78, IEC 60068-2-30: Operation: 5 % to 85 % at 30 °C (no condensation), storage / transport: 5 % to 95 % at 25 / 55 °C (no condensation) |
Vibrations |
Vibration resistance during operation acc. to IEC 60068-2-6 | Tested to DIN IEC 60068-2-6: 10 Hz to 58 Hz: 0.075 mm, 58 Hz to 200 Hz: 9.8 m/s² (1 g) |
Shock testing |
Shock load during operation | Tested according to IEC 60068-2-27, IEC 60068-2-29: half-sine: 50 m/s² (5 g), 30 ms, 100 shocks per axis |
Operating systems |
Operating system | Windows 7 Ultimate (Multi-Language) 64-bit, Windows Embedded Standard 7 E/P 32-bit / 64-bit, Windows 10 |
pre-installed operating system | Yes |
without operating system | Yes; Optional |
pre-installed operating system |
Windows 7 | Yes; Ultimate 64 bit |
Windows 10 Enterprise | Yes; Windows 10 Enterprise 2016 LTSB, 64 bit, MUI |
last modified: | 03/13/2019 |