SIMATIC MP 377 pro 15" Touch multi panel, Windows CE 5.0 15" color TFT display 12 MB configuration memory configurable from WinCC flexible 2007
General information
Product type designationMP377 PRO
Customer-specific configurationNo
Display
Design of displayTFT
Screen diagonal15 in
Color displayYes
Number of colors65 536
Resolution (pixels)
Horizontal image resolution1 024 Pixel
Vertical image resolution768 Pixel
Backlighting
MTBF backlighting (at 25 °C)50 000 h
Control elements
Control elementsTouch screen
Keyboard fonts
System keysNo
Numeric keyboardYes
alphanumeric keyboardYes
hexadecimal keyboardYes
Touch operation
Design as touch screenYes; analog, resistive
Connection type
Type of connection for mouse/keyboard/barcode readerUSB / USB / USB
Installation type/mounting
Mounting positionvertical
maximum permissible angle of inclination without external ventilation45°
Supply voltage
Type of supply voltageDC
Input current
Current consumption (rated value)1.8 A
Starting current inrush I²t0.5 A²·s
Power
Active power input, typ.41 W
Memory
Type of memoryFlash / RAM
Memory available for user data12 288 kbyte
Time of day
Clock
TypeHardware clock, battery backup, synchronizable
retentiveYes; via Goldkap for at least 6 weeks
synchronizableYes
Interfaces
Interfaces/bus type1x RS 422, 1x RS 485, 2x Ethernet (RJ45)
Number of industrial Ethernet interfaces2
Number of RS 485 interfaces1
Number of RS 422 interfaces1
Number of USB interfaces2; Up to 1 GB respectively
CF card slot1x CF card slot
Multimedia card/SD card slot1x Multimedia Card slot, up to 128 MB
Protocols
Supports protocol for PROFINET IOYes
PROFIsafeNo
PROFIBUSYes
MPIYes
Protocols (Ethernet)
TCP/IPYes
Protocols (terminal link)
Sm@rtServerYes
Further protocols
EtherNet/IPNo
MODBUSYes
other bus systemsYes
Degree and class of protection
IP (at the front)IP65
NEMA (front)NEMA 4 (when installed)
IP (rear)IP65
Standards, approvals, certificates
CertificationsCE, cULus, C-TICK, NEMA 4
cULusYes
Suitable for safety functionsNo
Use in hazardous areas
ATEX Zone 22No
FM Class I Division 2No
Ambient conditions
Ambient temperature during operation
min.0 °C
max.45 °C
Ambient temperature during storage/transportation
min.-20 °C
max.60 °C
Relative humidity
Operation, max.85 %
Operating systems
pre-installed operating systemWindows CE
Configuration
Message indicatorYes
Alarm system (incl. buffer and acknowledgment)Yes
Process value display (output)Yes
Process value default (input) possibleYes
Recipe managementYes
Configuration software
Configuration toolWinCC flexible Standard Version 2008 or higher (to be ordered separately)
STEP 7 Basic (TIA Portal)No
STEP 7 Professional (TIA Portal)No
WinCC flexible CompactNo
WinCC flexible StandardYes
WinCC flexible AdvancedYes
WinCC Basic (TIA Portal)No
WinCC Comfort (TIA Portal)Yes
WinCC Advanced (TIA Portal)Yes
WinCC Professional (TIA Portal)Yes
Languages
Online languages
Number of online/runtime languages5
Project languages
Languages per project32
Functionality under WinCC (TIA Portal)
LibrariesYes
Task plannerYes
Help systemYes
Number of characters per info text70
Message system
Number of alarm classes32
Number of messages4 000
Bit messagesYes
— Number of bit messages4 000
Analog messagesYes
— Number of analog messages4 000
Telegram message procedure Alarm SYes
System messages HMIYes
System messages PLCYes
System messages, other (SIMATIC S7, Sinumerik, Simotion, etc.)Yes
Lines1
Number of characters per message80
Number of process values per message8
Message indicatorYes
First/last valueYes
Recipe management
Number of recipes500
Data records per recipe1 000
Entries per data record1 000
Recipe memory128 KB integrated Flash, expandable
Variables
Number of variables per device4 096; Configuration with WinCC flexible 2008 and higher
Number of variables per screen400
Number of variables2 000
Initial values2 048
Type Date & Time2 048
Limit valuesYes
MultiplexingYes
StructuresYes
Images
Number of configurable images500
Permanent window/defaultYes
Start screen configurableYes
Image selection by PLCYes
Image number in the PLCYes
Image objects
Text objects30000 text elements
Number of I/O fields per image400
Number of date/time fields400
ReturnYes
Graphics objectBit maps, icons, vector graphics
— Icons2 000
Complex image objects
Status/controlWith SIMATIC S7
dynamic objectsDiagrams, bar graphs, sliders, analog display, invisible buttons
— Number of objects per project2 000
— Number of curve diagrams per image20
MethodsTrend / profile
Bar graphs
— Number of bars per chart20
Sliders
— Number of slides per image20
Pointer instruments
— Number of analog indicators per image20
Limit value linesYes
Number of alphanumerical fields300
— alphanumeric fields per image400
Number of numerical fields2 048
— numerical fields per image400
Number of password fields2 048
Number of visible switches per project400
— visible switches per image400
— hidden switches per image400
Number of status switches per project400
— Number of status switches per image400
Number of selector switches per project400
— Selector switches per image400
Number of signal lamps per project400
— Signal lamps per image400
Attributes for dynamic objects
Color changeYes
X/Y movementYes
HideYes
Lists
Number of text lists per project500
Number of text lists per image400
Number of entries per text list256
Number of graphics lists per project500
Number of graphic lists per image400
Number of entries per graphics list256
Archiving
Number of archives per device50
Number of measuring points per project50
Number of entries per archive50 000
Message archiveYes
Process value archiveYes
Archiving methodsSequential log, circular log, alarm log, process value archive
— Sequential archiveYes
— Short-term archiveYes
Memory locationCF card, SD/MMC card, Ethernet
— CF cardYes
— EthernetYes
Data storage formatCSV file, readable, e.g. with MS Excel, MS Access
— CSVYes
external evaluationReadable, e.g. with MS Excel, MS Access, etc.
Size of archivedepending on free memory on ext. card/stick or on free hard disk space via network drive
Online evaluationvia trends
— using trend curvesNo
Filters
cyclicYes
ToleranceYes
ChangeYes
Security
Number of user groups50
Number of user rights32
Password export/importYes
Data carrier support
CF cardYes
Hard diskYes
Logging through printer
Recording/PrintingAlarms, report (shift report), color print, hardcopy
Transfer (upload/download)
Transfer of configurationMPI/PROFIBUS DP, serial, USB, Ethernet, by means of external storage medium, automatic transfer recognition
Process coupling
Connection to controllerS5, S7-200, S7-300/400, TI 505, Win AC, PC (TCP/IP), SINUMERIK, SIMOTION, Allen Bradley (DF1), Allen Bradley (DF485), Mitsubishi (FX), OMRON (LINK/Multilink), Modicon (Modbus), further non-Siemens drivers, see chapter "System interfaces"
S7-1200Yes
S7-1500Yes
S7-200Yes
— PPI (point-to-point)Yes
— PPI networkYes
— MPIYes
— PROFIBUS DPYes
S7-300/400Yes
— MPIYes
— PROFIBUS DPYes
— PROFINETYes
S5Yes
— PROFIBUS DPYes
TI 505Yes
Allen Bradley (DF1)Yes
Allen Bradley (DF485)Yes
Mitsubishi (FX)Yes
Mitsubishi (MP4)Yes
Telemecanique (Uni-Telway)Yes
OMRON (LINK/Multilink)Yes
Modicon (Modbus)Yes
GE-Fanuc (SNP)Yes
Functions
TAB sequenceYes
Calculating functionsYes
AnimateYes
Service tools/configuration aids
Clean screenYes
Touch calibrationYes
Backup/Restore manuallyYes
SimulationYes
Device switchoverYes
Delta transferYes
Monitoring function for battery and memoryYes
Expandability/openness
Open Platform ProgramYes
Peripherals/Options
PeripheralsPrinter, card reader, barcode reader
SIMATIC HMI MM memory card: Multi Media CardYes
SIMATIC HMI SD memory card: Secure Digital memory cardYes
USB memoryYes
Additional software components loadableYes
Dimensions
Width of the housing front400 mm
Height of housing front310 mm
Overall depth98.5 mm
Weights
Weight (without packaging)7.25 kg
Other
free hotlineYes
last modified:03/13/2019