6AG3111-1SM30-0AB0-ZD30M10
SINVERT PVS2000 12DC 50HZ B

From SIEMENS

SINVERT PVS2000 INVERTER FOR PV, GRID CONNECT. MV TRANS, IEC 50HZ, 3P, STANDARD MPP, UMAX 820VDC, 12 DC-INPUTS, IP20, AIR COOLING, PV FIELD GROUNDING POS. POLE, SYMMETRY MONITORING
General technical data:
Product brand nameSINVERT
Product type designationSINVERT PVS2000
Product designationphotovoltaic inverter
Performance class for PV inverters2000
Efficiency maximum possible%98.4
Efficiency
acc. to Euro%98.3
acc. to CEC%98.3
Design of PV inverter unitmaster-slave combination
Number of PV inverter sub-units4
Type of installationindoor installation
Protection class IPIP20
Operating resource protection classI
Design of the interface for communicationEthernet
A-rated sound power level maximumdB80
Design of the displayLCD-TFT
National language on the display screen selectableEnglish, German
Connection method for PV inverterswithout transformer
Outputs:
Phase number3
Output voltage on the AC side for infeed operation Rated valueV288
Output voltage on the AC side for infeed operationV244.8 ... 316.8
Power factor at rated active power value Rated value1
Supplied active power on the AC side
in permanent operation Rated valueW2 000 000
maximumW2 000 000
Current supplied on the AC side maximumA4 008
Line frequency for infeed operation Rated valueHz50
Line frequency for infeed operationHz49 ... 51
Inductive power factor minimum0.95
Capacitive power factor minimum0.95
Relative residual ripple of AC current at rated AC active power with off-load grid maximum%2
Grounding concept on the AC sideIT
Design of the overvoltage protection on the AC sidetype 1/2
Inputs:
MPP voltageV450 ... 750
Consumed active power on the DC side Rated valueW2 052 000
Input voltage on the DC side
for start of the infeed modeV600
for possible infeed operationV450 ... 750
Rated valueV450
maximum permissibleV820
Number of inputs on the DC side12
Input current per DC input maximumA368
Total consumed power on the DC side maximumA4 412
Overcurrent strength per DC input Rated valueA368
Design of the overvoltage protection on the DC sidetype 2
Auxiliary circuit:
Auxiliary voltage Rated valueV400
Consumed active power from external auxiliary voltage
for infeed operation
— without cabinet heating maximumW10 600
in night-time operating mode
— without cabinet heating maximumW760
— with cabinet heating maximumW1 760
Grounding concept for external auxiliary power supplyTN-S
Auxiliary voltage frequency Rated valueHz50
Ambient conditions:
Installation altitudem0 ... 2 000
Installation altitude at rated active powerm0 ... 1 000
Incoming air temperature at rated active power value maximum°C40
Ambient temperature
during operation°C0 ... 50
during storage°C-25 ... +70
during transport°C-25 ... +70
Relative humidity without condensation during operation%0 ... 95
Relative humidity
during storage maximum%95
during transport maximum%95
Environmental category3K3
Type of coolingForced-air cooling via fan
Cooling air flowm³/h26 000
Type of ventilationair intake cabinet front/air outlet cabinet top
Mechanical data:
Mounting positionvertical
Width of PV inverter subunitmm2 700
Height of PV inverter subunitmm2 100
Depth of PV inverter subunitmm730
Weight of the single devicekg2 089
Mounting typeFloor mounting installation

External links