| SIPLUS HMI TP700 OUTDOOR RAIL -25°C...60°C T1 with 70°C for 10 min with conformal coating based on 6AV2124-0GC13-0AX0. TP700 Comfort Outdoor, Comfort "Panel, Touch operation, 7""" widescreen TFT display, 16 million colors, PROFINET interface, MPI/PROFIBUS DP interface, 12 MB configuration memory, Windows CE 6.0, configurable WINCC Comfort V13 SP1 and higher, HSP |
General information |
Product type designation | TP700 Outdoor |
Display |
Design of display | TFT, bonded, daylight-readable |
Screen diagonal | 7 in |
Display width | 152.4 mm |
Display height | 91.4 mm |
Number of colors | 16 777 216 |
Resolution (pixels) |
Horizontal image resolution | 800 Pixel |
Vertical image resolution | 480 Pixel |
Backlighting |
MTBF backlighting (at 25 °C) | 50 000 h |
Backlight dimmable | Yes; LED, can be dimmed manually or automatically |
Control elements |
Keyboard fonts |
Function keys | |
— Number of function keys | 0 |
Keys with LED | No |
System keys | No |
Numeric keyboard | Yes; Onscreen keyboard |
alphanumeric keyboard | Yes; Onscreen keyboard |
Touch operation |
Design as touch screen | Yes; analog, resistive |
Expansions for operator control of the process |
DP direct LEDs (LEDs as S7 output I/O) | |
— F1...Fx | 0 |
Direct keys (keys as S7 input I/O) | |
— F1...Fx | 0 |
Direct keys (touch buttons as S7 input I/O) | 32 |
Installation type/mounting |
Mounting position | vertical |
Mounting in portrait format possible | Yes |
Mounting in landscape format possible | Yes |
maximum permissible angle of inclination without external ventilation | 35° |
Supply voltage |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
Current consumption (rated value) | 0.7 A |
Starting current inrush I²t | 0.5 A²·s |
Power |
Active power input, typ. | 17 W |
Processor |
Processor type | X86 |
Memory |
Flash | Yes |
RAM | Yes |
Memory available for user data | 12 Mbyte |
Type of output |
Info LED | No |
Power LED | No |
Error LED | No |
Acoustics | |
Buzzer | No |
Speaker | Yes |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
Software clock | No |
retentive | Yes; Back-up duration typically 6 weeks |
synchronizable | Yes |
Interfaces |
Number of industrial Ethernet interfaces | 2 |
Number of RS 485 interfaces | 1; RS 422 / 485 combined |
Number of RS 422 interfaces | 1 |
Number of RS 232 interfaces | 0 |
Number of USB interfaces | 2; USB 2.0 |
USB Mini B | 1; 5-pole |
Number of 20 mA interfaces (TTY) | 0 |
Number of parallel interfaces | 0 |
Number of other interfaces | 0 |
Number of SD card slots | 2 |
With software interfaces | No |
Industrial Ethernet |
Industrial Ethernet status LED | 2 |
Number of ports of the integrated switch | 2 |
Protocols |
PROFINET | Yes |
Supports protocol for PROFINET IO | Yes |
IRT | Yes |
PROFIBUS | Yes |
MPI | Yes |
Protocols (Ethernet) |
TCP/IP | Yes |
DHCP | Yes |
SNMP | Yes |
DCP | Yes |
LLDP | Yes |
WEB characteristics |
HTTP | Yes |
HTTPS | No |
HTML | Yes |
XML | No |
CSS | Yes |
Active X | No |
JavaScript | Yes |
Java VM | No |
Redundancy mode |
MRP | Yes |
Further protocols |
CAN | No |
EtherNet/IP | Yes |
MODBUS | Yes |
Isolation |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) |
EMC |
Emission of radio interference acc. to EN 55 011 |
Limit class A, for use in industrial areas | Yes |
Limit class B, for use in residential areas | No |
Degree and class of protection |
IP (at the front) | IP66 |
Enclosure Type 4 at the front | Yes |
Enclosure Type 4x at the front | Yes |
IP (rear) | IP20 |
Standards, approvals, certificates |
CE mark | Yes |
Railway application |
EN 50121-3-2 | Yes; EMC for rail vehicles |
EN 50121-4 | Yes; EMC for signal and telecommunications systems |
EN 50124-1 | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
EN 50125-1 | Yes; Rail vehicles - see ambient conditions |
EN 50125-2 | Yes; Stationary electrical equipment - see ambient conditions |
EN 50125-3 | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
EN 50155 | Yes; Rail vehicles - temperature class T1, horizontal and vertical mounting position, salt spray class ST2 |
EN 61373 | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
Fire protection acc. to EN 45545-2 | Yes; Rail vehicles - verification on request |
Ambient conditions |
Suited for indoor use | Yes |
Suited for outdoor use | Yes |
Ambient temperature during operation |
Operation (vertical installation) | |
— For vertical installation, min. | -30 °C; = Tmin |
— For vertical installation, max. | 60 °C; (55 °C, see entry ID: 64847814) |
Operation (max. tilt angle) | |
— At maximum tilt angle, min. | -30 °C; = Tmin |
— At maximum tilt angle, min. | 50 °C; = Tmax |
Operation (vertical installation, portrait format) | |
— For vertical installation, min. | -30 °C; = Tmin |
— For vertical installation, max. | 50 °C; = Tmax |
Operation (max. tilt angle, portrait format) | |
— At maximum tilt angle, min. | -30 °C; = Tmin |
— At maximum tilt angle, min. | 45 °C; = Tmax |
Ambient temperature during storage/transportation |
min. | -30 °C |
max. | 70 °C |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 2 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Coolants and lubricants |
— Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on land craft, rail vehicles and special-purpose vehicles |
— to biologically active substances according to EN 60721-3-5 | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
— to chemically active substances according to EN 60721-3-5 | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); * |
— to mechanically active substances according to EN 60721-3-5 | Yes; Class 5S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Conformal coating |
Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high availability |
Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
Electronic equipment on rolling stock acc. to EN 50155 | Yes; Class PC2 protective coating acc. to EN 50155:2017 |
Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
Operating systems |
proprietary | No |
pre-installed operating system |
Windows CE | Yes |
Configuration |
Message indicator | Yes |
Alarm system (incl. buffer and acknowledgment) | Yes |
Process value display (output) | Yes |
Process value default (input) possible | Yes |
Recipe management | Yes |
Configuration software |
STEP 7 Basic (TIA Portal) | No |
STEP 7 Professional (TIA Portal) | No |
WinCC flexible Compact | No |
WinCC flexible Standard | No |
WinCC flexible Advanced | No |
WinCC Basic (TIA Portal) | No |
WinCC Comfort (TIA Portal) | Yes |
WinCC Advanced (TIA Portal) | Yes |
WinCC Professional (TIA Portal) | Yes |
Languages |
Online languages |
Number of online/runtime languages | 32 |
Project languages |
Languages per project | 32 |
Functionality under WinCC (TIA Portal) |
Libraries | Yes |
Applications/options | |
Web browser | Yes |
Pocket Word | Yes |
Pocket Excel | Yes |
PDF Viewer | Yes |
Media Player | Yes |
SIMATIC WinCC Sm@rtServer | Yes |
SIMATIC WinCC Audit | Yes |
Number of Visual Basic Scripts | Yes |
Task planner | |
time-controlled | Yes |
task-controlled | Yes |
Help system | |
Number of characters per info text | 70 |
Message system |
Number of alarm classes | 32 |
Bit messages | |
— Number of bit messages | 4 000 |
Analog messages | |
— Number of analog messages | 200 |
S7 alarm number procedure | Yes |
System messages HMI | Yes |
System messages, other (SIMATIC S7, Sinumerik, Simotion, etc.) | Yes |
Number of characters per message | 80 |
Number of process values per message | 8 |
Acknowledgment groups | Yes |
Message indicator | Yes |
Message buffer | |
— Number of entries | 1 024 |
— Circulating buffer | Yes |
— retentive | Yes |
— maintenance-free | Yes |
Recipe management |
Number of recipes | 300 |
Data records per recipe | 500 |
Entries per data record | 1 000 |
Size of internal recipe memory | 2 Mbyte |
Recipe memory expandable | Yes |
Variables |
Number of variables per device | 2 048 |
Number of variables per screen | 400 |
Limit values | Yes |
Multiplexing | Yes |
Structures | Yes |
Arrays | Yes |
Images |
Number of configurable images | 500 |
Permanent window/default | Yes |
Global image | Yes |
Image selection by PLC | Yes |
Image number in the PLC | Yes |
Image objects |
Number of objects per image | 400 |
Text fields | Yes |
I/O fields | Yes |
Graphic I/O fields (graphics list) | Yes |
Symbolic I/O fields (text list) | Yes |
Date/time fields | Yes |
Switches | Yes |
Buttons | Yes |
Graphic display | Yes |
Icons | Yes |
Geometric objects | Yes |
Complex image objects |
Number of complex objects per screen | 20 |
Alarm view | Yes |
Trend view | Yes |
User view | Yes |
Status/control | Yes |
Sm@rtClient view | Yes |
Recipe view | Yes |
f(x) trend view | Yes |
System diagnostics view | Yes |
Media Player | Yes |
Bar graphs | Yes |
Sliders | Yes |
Pointer instruments | Yes |
Analog/digital clock | Yes |
Lists |
Number of text lists per project | 500 |
Number of entries per text list | 500 |
Number of graphics lists per project | 500 |
Number of entries per graphics list | 500 |
Archiving |
Number of archives per device | 50 |
Number of entries per archive | 20 000 |
Message archive | Yes |
Process value archive | Yes |
Archiving methods | |
— Sequential archive | Yes |
— Short-term archive | Yes |
Memory location | |
— Memory card | Yes |
— USB memory | Yes |
— Ethernet | Yes |
Data storage format | |
— CSV | Yes |
— TXT | Yes |
— RDB | Yes |
Security |
Number of user groups | 50 |
Number of user rights | 32 |
Number of users | 50 |
Password export/import | Yes |
SIMATIC Logon | Yes |
Logging through printer |
Alarms | Yes |
Report (shift log) | Yes |
Hardcopy | Yes |
Electronic print to file | Yes; PDF, HTML |
Character sets |
Keyboard fonts | |
— US English | Yes |
Transfer (upload/download) |
MPI/PROFIBUS DP | Yes |
USB | Yes |
Ethernet | Yes |
using external storage medium | Yes; Backup/restore |
Process coupling |
S7-1200 | Yes |
S7-1500 | Yes |
S7-200 | Yes |
S7-300/400 | Yes |
LOGO! | Yes |
WinAC | Yes |
SINUMERIK | Yes; with SINUMERIK option package |
SIMOTION | Yes |
Allen Bradley (EtherNet/IP) | Yes |
Allen Bradley (DF1) | Yes |
Mitsubishi (MC TCP/IP) | Yes |
Mitsubishi (FX) | Yes |
OMRON (FINS TCP) | No |
OMRON (LINK/Multilink) | Yes |
Modicon (Modbus TCP/IP) | Yes |
Modicon (Modbus) | Yes |
OPC UA Client | Yes |
OPC UA Server | Yes |
Service tools/configuration aids |
Backup/Restore manually | Yes |
Backup/Restore automatically | Yes |
Simulation | Yes |
Device switchover | Yes |
Peripherals/Options |
Peripherals | |
Printer | Yes |
SIMATIC HMI MM memory card: Multi Media Card | Yes |
SIMATIC HMI SD memory card: Secure Digital memory card | Yes |
SIMATIC HMI CF memory card Compact Flash Card | No |
USB memory | Yes |
SIMATIC IPC USB Flashdrive (USB stick) | Yes |
SIMATIC HMI USB stick | Yes |
Network camera | Yes |
Mechanics/material |
Enclosure material (front) | |
Plastic | No |
Aluminum | Yes; Powder-coated, UV resistant |
Stainless steel | No |
Dimensions |
Width of the housing front | 214 mm |
Height of housing front | 158 mm |
Mounting cutout, width | 197 mm |
Mounting cutout, height | 141 mm |
Overall depth | 67 mm |
Weights |
Weight without packaging | 1.5 kg |
Weight incl. packaging | 1.7 kg |
Other |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |
last modified: | 03/13/2019 |