| SIPLUS DC-USV-MODUL 24V/40A |
SIPLUS PS DC UPS module 24 V/40 A -25...+70°C with conformal coating based on 6EP1931-2FC21 . Uninterruptible Power supply without interface Input: 24 V DC/43 A Output: 24 V DC/40 A |
Input |
Supply voltage at DC Rated value | 24 V |
Voltage curve at input | DC |
input voltage range | 22 ... 29 V DC |
Adjustable response value voltage for buffer connection preset | 22.5 V |
Adjustable response value voltage for buffer connection | 22 ... 25.5 V; Adjustable in 0.5 V increments |
Input current at rated input voltage 24 V Rated value | 40 A; + approx. 2.6 A with empty battery |
Mains buffering |
Type of energy storage | with batteries |
Design of the mains power cut bridging-connection | Dependent on connected battery and load current, see selection table battery module and mains buffering times as well as the relevant important information notes! |
Charging current | 1 A, 2 A |
adjustable charging current maximum Note | factory setting approx. 2 A |
Output |
Output voltage | |
in normal operation at DC Rated value | 24 V |
in buffering mode at DC Rated value | 24 V |
Formula for output voltage | Vin - approx. 0.5 V |
ON-delay time typical | 1 s |
Voltage increase time of the output voltage typical | 360 ms |
Output voltage in buffering mode at DC | 19 ... 28.5 V |
Output current | |
Rated value | 40 A |
in normal operation | 0 ... 40 A |
in buffering mode | 0 ... 40 A |
Peak current | 42 A |
Supplied active power typical | 960 W |
Efficiency |
Efficiency in percent | |
at rated output current for rated value of the output current typical | 97.2 % |
in case of accumulator operation typical | 96.9 % |
Power loss [W] | |
at rated output current for rated value of the output current typical | 28.6 W |
in case of accumulator operation typical | 33.6 W |
Protection and monitoring |
Product function | |
reverse polarity protection against energy storage unit polarity reversal | Yes |
reverse polarity protection against input voltage polarity reversal | Yes |
Signaling |
Display version | |
for normal operation | Normal operation: LED green (OK), floating changeover contact "Bat/OK" to setting "OK" ("OK" means: Voltage of the supplying power supply unit is greater than cut-in threshold set at the DC UPS module); Lack of buffer standby: LED red (alarm), floating changeover contact "Alarm/Bat" to setting "Alarm"; Battery replacement required: LED red (alarm) flashing with approx. 0.25 Hz, floating changeover contact "Alarm/Bat" switching with approx. 0.25 Hz; Energy storage > 85%: LED green (Bat > 85%), floating NO contact "Bat > 85" closed; Permissible contact current capacity: DC 60 V/1 A or AC 30 V /1 A |
in buffering mode | Buffered mode: LED yellow (Bat), floating changeover contact "OK/Bat" to setting "Bat"; Prewarning battery voltage < 20.4 VDC: LED red (alarm), floating changeover contact "Alarm/Bat" to setting "Alarm"; Energy storage > 85%: LED green (Bat > 85%), floating NO contact "Bat > 85" closed |
Interface |
Product component PC interface | No |
Design of the interface | without |
Safety |
Galvanic isolation between entrance and outlet | No |
Operating resource protection class | Class III |
Certificate of suitability | |
CE marking | Yes |
Protection class IP | IP20 |
EMC |
Standard | |
for emitted interference | EN 55022 Class B |
for interference immunity | EN 61000-6-2 |
Operating data |
Ambient temperature | |
during operation | -25 ... +70 °C; with natural convection |
during transport | -40 ... +85 °C |
during storage | -40 ... +85 °C |
Relative humidity with condensation maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance to biologically active substances conformity acc. to EN 60721-3-3 | Yes |
Resistance to chemically active substances conformity acc. to EN 60721-3-3 | Yes |
Resistance to mechanically active substances conformity acc. to EN 60721-3-3 | Yes |
Mechanics |
Type of electrical connection | screw-type terminals |
at input | 24 V DC: 2 screw terminals for 0.33 ... 10 mm²/22 ... 7 AWG |
at output | 24 V DC: 2 screw terminals for 0.33 ... 10 mm²/22 ... 7 AWG |
for battery module | 24 V DC: 2 screw terminals for 0.33 ... 10 mm²/22 ... 7 AWG |
for control circuit and status message | 10 screw terminals for 0.5 ... 2.5 mm²/20 ... 13 AWG |
Width of the enclosure | 102 mm |
Height of the enclosure | 125 mm |
Depth of the enclosure | 125 mm |
Required spacing | |
top | 50 mm |
bottom | 50 mm |
left | 0 mm |
right | 0 mm |
Net weight | 1.1 kg |
Product feature of the enclosure housing for side-by-side mounting | Yes |
Mounting type | Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories | Battery module |
MTBF at 40 °C | 522 739 h |
Reference code acc. to DIN EN 81346-2 | T |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| |