| SIPLUS PS PSU8200 |
SIPLUS PSU8200 3-ph. 24 V DC 40 A -25...+70°C with conformal coating based on 6EP1437-3BA10 . Stabilized power supplies Input: 400-500V 3 AC Output: 24 V DC/40 A |
Input |
Input | 3-phase AC |
Rated voltage value Vin rated | 400 ... 500 V |
Voltage range AC | 320 ... 575 V |
Wide-range input | Yes |
Mains buffering at Iout rated, min. | 15 ms; at Vin = 400 V |
Rated line frequency 1 | 50 Hz |
Rated line frequency 2 | 60 Hz |
Rated line range | 47 ... 63 Hz |
Input current | |
at rated input voltage 400 V | 2.6 A |
at rated input voltage 500 V | 2.1 A |
Switch-on current limiting (+25 °C), max. | 56 A |
I²t, max. | 2.24 A²·s |
Built-in incoming fuse | none |
Protection in the mains power input (IEC 898) | Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) |
Output |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24 V |
Total tolerance, static ± | 3 % |
Static mains compensation, approx. | 0.1 % |
Static load balancing, approx. | 0.2 % |
Residual ripple peak-peak, max. | 100 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 200 mV |
Adjustment range | 24 ... 28.8 V |
Product function Output voltage adjustable | Yes |
Output voltage setting | via potentiometer; max. 960 W |
Status display | Green LED for 24 V OK |
Signaling | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
Voltage increase time of the output voltage maximum | 500 ms |
Rated current value Iout rated | 40 A |
Current range | 0 ... 40 A |
Note | +60 ... +70 °C: Derating 3.75%/K |
Supplied active power typical | 960 W |
Short-term overload current | |
at short-circuit during operation typical | 120 A |
Duration of overloading capability for excess current | |
at short-circuit during operation | 25 ms |
Constant overload current | |
on short-circuiting during the start-up typical | 44 A |
Parallel switching for enhanced performance | Yes; switchable characteristic |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency |
Efficiency at Vout rated, Iout rated, approx. | 92 % |
Power loss at Vout rated, Iout rated, approx. | 83 W |
Closed-loop control |
Dynamic mains compensation (Vin rated ±15 %), max. | 1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 3 % |
Setting time maximum | 10 ms |
Protection and monitoring |
Output overvoltage protection | < 35 V |
Current limitation, typ. | 44 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Alternatively, constant current characteristic approx. 44 A or latching shutdown |
Enduring short circuit current RMS value | |
typical | 44 A |
Overcurrent overload capability in normal operation | overload capability 150 % Iout rated up to 5 s/min |
Overload/short-circuit indicator | LED yellow for "overload", LED red for "latching shutdown" |
Safety |
Primary/secondary isolation | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I |
Leakage current | |
maximum | 3.5 mA |
CE mark | Yes |
Degree of protection (EN 60529) | IP20 |
EMC |
Emitted interference | EN 55022 Class B |
Supply harmonics limitation | EN 61000-3-2 |
Noise immunity | EN 61000-6-2 |
Operating data |
Ambient temperature | |
during operation | -25 ... +70 °C |
— Note | with natural convection |
during transport | -40 ... +85 °C |
during storage | -40 ... +85 °C |
Humidity class according to EN 60721 | Climate class 3K8H |
Relative humidity with condensation maximum | 100 %; Relative humidity, incl. condensation/frost permitted (no commissioning under condensation conditions) |
Resistance to biologically active substances conformity acc. to EN 60721-3-3 | Yes |
Resistance to chemically active substances conformity acc. to EN 60721-3-3 | Yes |
Resistance to mechanically active substances conformity acc. to EN 60721-3-3 | Yes |
Mechanics |
Connection technology | screw-type terminals |
Connections | |
Supply input | L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded |
Output | +, -: 2 screw terminals each for 0.33 ... 10 mm² |
Auxiliary | 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm² |
Width of the enclosure | 150 mm |
Height of the enclosure | 125 mm |
Depth of the enclosure | 150 mm |
Required spacing | |
top | 50 mm |
bottom | 50 mm |
left | 0 mm |
right | 0 mm |
Weight, approx. | 3.4 kg |
Product feature of the enclosure housing for side-by-side mounting | Yes |
Installation | Snaps onto DIN rail EN 60715 35x15 |
Electrical accessories | Buffer module |
Mechanical accessories | Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20 |
MTBF at 40 °C | 885 739 h |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| |