General information
Product type designationPS 407
Supply voltage
Rated value (DC)
120 V DCYes
230 V DCYes
permissible range, lower limit (DC)88 V
permissible range, upper limit (DC)300 V
Rated value (AC)
120 V ACYes
230 V ACYes
permissible range, lower limit (AC)85 V
permissible range, upper limit (AC)264 V
Line frequency
Rated value 50 HzYes
Rated value 60 HzYes
permissible range, lower limit47 Hz
permissible range, upper limit63 Hz
Mains buffering
Mains/voltage failure stored energy time20 ms
Mains buffering according to NAMUR recommendationYes
Input current
Rated value at 110 V DC1 A; at 120 V DC
Rated value at 230 V DC0.5 A
Rated value at 120 V AC0.9 A
Rated value at 230 V AC0.5 A
Inrush current, max.63 A; Full width at half maximum 1 ms
Output voltage
Type of output voltageDC
Rated value (DC)
5 V DCYes
24 V DCYes
Output current
for backplane bus (5 V DC), max.10 A; no base load required
for backplane bus (24 V DC), max.1 A; idling-proof
Short-circuit protectionYes
Power
Active power input, typ.95 W
Power loss
Power loss, typ.20 W
Battery
Backup battery
Backup battery (optional)Yes; 2x lithium AA; 3.6 V / 2.3 Ah
Hardware configuration
Slots
required slots2
Potential separation
primary/secondaryYes
EMC
Compliance with line harmonic distortion limits
Compliance with line harmonic distortion acc. to IEC 61000-3-2, IEC 61000-3-3Yes
Degree and class of protection
Equipment protection classI, with protective conductor
Standards, approvals, certificates
FM approvalYes; Ta: 0 °C to 60 °C T4
Connection method
Design of electrical connection3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm
Dimensions
Width50 mm
Height290 mm
Depth217 mm
Weights
Weight, approx.1 200 g