6AG1341-1AH02-7AE0
SIPLUS S7-300 CP341 RS232C

From SIEMENS

SIPLUS S7-300, CP 341 -25...+70 °C with conformal coating based on 6ES7341-1AH02-0AE0 . Communications processor with RS232C interface (RS-232-C) incl. configuration package auf CD-ROM
General information
Product type designationCP 341
Supply voltage
Rated value (DC)
24 V DCYes
Input current
from supply voltage L+, max.100 mA
from backplane bus 5 V DC, max.70 mA
Power loss
Power loss, typ.1.6 W
Power loss, max.2.4 W
Interfaces
Number of interfaces1; Isolated
Interface physics, RS 232C (V.24)Yes
Transmission rate, min.0.3 kbit/s
Transmission rate, max.115.2 kbit/s
Point-to-point connection
Cable length, max.15 m
supported printersSerial printers
Connector type9-pin sub D connector
Integrated protocol driver
— 3964 (R)Yes
— ASCIIYes
— RK512Yes
Telegram length, max.
— 3964 (R)4 096 byte
— ASCII4 096 byte
— RK 5124 096 byte
Transmission speed, RS 232
— with 3964 (R) protocol, max.115.2 kbit/s
— with ASCII protocol, max.115.2 kbit/s
— with printer driver, max.115.2 kbit/s
— with RK 512 protocol, max.115.2 kbit/s
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Software
Block
FB length in RAM, max.6 100 byte; Data communication, sending and receiving
Connection method
Design of electrical connection for supply voltage3 screw-type terminals: L+, M, GND
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.300 g
last modified:03/13/2019