| ***Spare part*** SIPLUS S7-300 SM 336F 6AI 40-pole for medial exposure based on 6ES7336-1HE00-0AB0 |
Supply voltage |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
From power supply L+, typ. | 160 mA |
from backplane bus 5 V DC, max. | 90 mA |
Power loss |
Power loss, typ. | 4.25 W |
Analog inputs |
Number of analog inputs | 6 |
For voltage measurement | 4 |
permissible input voltage for voltage input (destruction limit), max. | 30 V |
permissible input current for current input (destruction limit), max. | 40 mA |
Input ranges |
Voltage | Yes |
Current | Yes |
Input ranges (rated values), voltages |
0 to +10 V | Yes |
Input resistance (0 to 10 V) | 59 kΩ |
Input ranges (rated values), currents |
0 to 20 mA | Yes |
Input resistance (0 to 20 mA) | 107 Ω |
4 mA to 20 mA | Yes |
Input resistance (4 mA to 20 mA) | 107 Ω |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 14 bit |
Integration time (ms) | 20 ms (at 50 Hz); 16.66 ms (at 60 Hz) |
Interference voltage suppression for interference frequency f1 in Hz | 38 dB |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | Yes |
for current measurement as 4-wire transducer | Yes |
Errors/accuracies |
Operational error limit in overall temperature range |
Voltage, relative to input range, (+/-) | 0.48 % |
Current, relative to input range, (+/-) | 0.48 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input range, (+/-) | 0.4 % |
Current, relative to input range, (+/-) | 0.4 % |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Alarms |
Diagnostic alarm | Yes; Parameterizable |
Diagnostic messages |
Diagnostic information readable | Yes |
Diagnostics indication LED |
Fail-safe operation | Yes |
Group error SF (red) | Yes |
Encoder supply Vs (green) | Yes |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | Yes; only if sensors are externally supplied |
Isolation |
Isolation tested with | 500 V DC/350 V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
Requirement class according to DIN V 19250 | AK 6 |
acc. to EN 954 | Cat. 4 |
SIL acc. to IEC 61508 | SIL 3 |
Ambient conditions |
Ambient temperature during operation |
min. | 0 °C; = Tmin |
max. | 60 °C; = Tmax |
Altitude during operation relating to sea level |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method |
required front connector | 40-pin |
Dimensions |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Weights |
Weight, approx. | 480 g |
last modified: | 03/13/2019 |