6AG1322-1BH01-2AA0
SIPLUS S7-300 SM322 16DA/24VDC 0.5A

From SIEMENS

SIPLUS S7-300 SM322 - 20-POLE -25...+70°C with conformal coating with conformity EN50155 T1 CAT 1 KL A/B based on 6ES7322-1BH01-0AA0 . DIGITAL OUTPUT OPTIC. ISOLATED 16D0, 24V DC, 0.5A, SUM OF CURRENTS 4A/GROUP (8A/MODULE)
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.80 mA
from backplane bus 5 V DC, max.80 mA
Power loss
Power loss, typ.4.9 W
Digital outputs
Number of digital outputs16
Limitation of inductive shutdown voltage toL+ (-53 V)
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value0.5 A
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.4 A
— up to 60 °C, max.3 A
— up to 70 °C, max.3 A
vertical installation
— up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionNo
Alarms
Diagnostic alarmNo
Diagnostic messages
Wire-breakNo
Short-circuitNo
Fuse blownNo
missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)No
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Permissible potential difference
between different circuits75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50155Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007
Ambient conditions
Ambient temperature during operation
min.-25 °C
max.70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.190 g
last modified:03/25/2019