| SIPLUS ET 200M IM 153-4 PN IO -25...+70°C with conformal coating based on 6ES7153-4AA01-0XB0 . for max. 12 S7-300 modules, extended functions: Isochronous real-time Communication Class 1 and 2, module replacement without PG operation without MMC, maintenance Support of new IO modules |
General information |
Product type designation | IM 153-4 PN |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0302H |
Supply voltage |
Rated value (DC) | |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) |
Mains buffering |
Mains/voltage failure stored energy time | 5 ms |
Input current |
Current consumption, max. | 600 mA |
Inrush current, typ. | 4 A |
I²t | 0.09 A²·s |
Output voltage |
Rated value (DC) | 5 V |
Output current |
for backplane bus (5 V DC), max. | 1.5 A |
Power loss |
Power loss, typ. | 6 W |
Address area |
Addressing volume |
Inputs | 192 byte |
Outputs | 192 byte |
Hardware configuration |
Number of modules per DP slave interface, max. | 12 |
Protocols |
Bus protocol/transmission protocol | PROFINET IO |
Protocols (Ethernet) |
TCP/IP | Yes |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Connection to network LINK (green) | Yes |
Transmit/receive RX/TX (yellow) | Yes |
Potential separation |
Potential separation exists | Yes |
Isolation |
Isolation tested with | 500 V DC |
Degree and class of protection |
IP degree of protection | IP20 |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
Ambient temperature during storage/transportation |
min. | -40 °C |
max. | 70 °C |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions |
Width | 40 mm |
Height | 125 mm |
Depth | 118 mm |
Weights |
Weight, approx. | 215 g; approx. |
last modified: | 03/26/2019 |