6AG1153-2BA02-7XB0
SIPLUS_IM153-2

From SIEMENS

***Spare part*** SIPLUS ET 200M IM 153-2 (*BA02) -40...+70°C start up temperature: -25°C with conformal coating based on 6ES7153-2BA02-0XB0 Connection ET 200M for max. 12 S7-300 modules with redundancy capability, Timestamping suitable for isochronous mode Operation New features: up to 12 modules can be used Slave Initiative for Drive ES and Switch ES Expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals/slot
General information
Product type designationIM 153-2 DP ST
Vendor identification (VendorID)801Eh
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
external protection for power supply lines (recommendation)2,5 A
Mains buffering
Mains/voltage failure stored energy time5 ms
Input current
Current consumption, max.600 mA
Inrush current, typ.3 A
I²t0.1 A²·s
Output voltage
Rated value (DC)5 V
Output current
for backplane bus (5 V DC), max.1.5 A
Power loss
Power loss, typ.5.5 W
Address area
Addressing volume
Inputs244 byte
Outputs244 byte
Hardware configuration
Number of modules per DP slave interface, max.12
Time stamping
Accuracy1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules
Number of message buffers15
Messages per message buffer20
Number of stampable digital inputs, max.128; Max. 128 signals/station; max. 32 signals/slot
Time formatRFC 1119
Time resolution0.466 ns
Time interval for transmitting the message buffer if a message is present1 000 ms
Time stamp on signal changerising / falling edge as signal entering or exiting
Interfaces
Transmission procedureRS 485
PROFIBUS DP
Node addresses1 to 125 permitted
automatic detection of transmission rateYes
Output current, max.70 mA
Transmission rate, max.12 Mbit/s
SYNC capabilityYes
FREEZE capabilityYes
Direct data exchange (slave-to-slave communication)Yes; Sender
Design of electrical connection of PROFIBUS interface9-pin sub D
1. Interface
PROFIBUS DP slave
GSD fileSI04801.GSG
automatic baud rate searchYes
Protocols
Bus protocol/transmission protocolPROFIBUS DP to EN 50170
Protocols (Ethernet)
TCP/IPNo
Potential separation
Potential separation existsYes
Isolation
Isolation tested withIsolation voltage 500 V
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
FM approvalYes; CofC 3028431
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.-40 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL use
At cold restart, min.-25 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Configuration
Configuration software
STEP 7Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.360 g
last modified:03/28/2019