6AG1134-4GD00-2AB0
SIPLUS_ET200S 4 AI I 2WIRE

From SIEMENS

SIPLUS ET 200S EM 4 AI I 2-wire -25...+70°C with conformal coating based on 6ES7134-4GD00-0AB0 . "Electronic module 4-20 mA; 13" bit 15 mm width, for 2-wire transducer Cycle time 40 ms/module with SF LED (group fault)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.125 mA
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
presentYes
short-circuit proofYes; approx. 200 mA for module
Power loss
Power loss, typ.0.6 W
Address area
Address space per module
Address space per module, max.8 byte
Analog inputs
Number of analog inputs4
permissible input current for current input (destruction limit), max.30 mA; limited electronically
Cycle time (all channels) max.40 ms; 33 to 40 ms
Input ranges (rated values), currents
4 mA to 20 mAYes; Into 25 Ohm
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.13 bit; 4 to 20 mA: 13 bit
Integration time, parameterizableYes
Integration time (ms)16,67 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Smoothing of measured values
parameterizableYes; in 4 stages
Step: NoneYes; 1x cycle time
Step: lowYes; 4x cycle time
Step: MediumYes; 16x cycle time
Step: HighYes; 32x cycle time
Encoder
Connection of signal encoders
for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max.750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.003 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostic messages
Wire-breakYes; Measuring range 1 to 5 V only
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 byte
Diagnostics wire break1
Measurement type/range1
Group diagnostics1
Overflow/underflow1
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+No
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019

External links