| SIPLUS ET 200S EM 4 AI I 2-wire -25...+70°C with conformal coating based on 6ES7134-4GD00-0AB0 . "Electronic module 4-20 mA; 13" bit 15 mm width, for 2-wire transducer Cycle time 40 ms/module with SF LED (group fault) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 125 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Output voltage |
Power supply to the transmitters |
present | Yes |
short-circuit proof | Yes; approx. 200 mA for module |
Power loss |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
Address space per module, max. | 8 byte |
Analog inputs |
Number of analog inputs | 4 |
permissible input current for current input (destruction limit), max. | 30 mA; limited electronically |
Cycle time (all channels) max. | 40 ms; 33 to 40 ms |
Input ranges (rated values), currents |
4 mA to 20 mA | Yes; Into 25 Ohm |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Measurement principle | integrating |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 13 bit; 4 to 20 mA: 13 bit |
Integration time, parameterizable | Yes |
Integration time (ms) | 16,67 / 20 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Smoothing of measured values |
parameterizable | Yes; in 4 stages |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 4x cycle time |
Step: Medium | Yes; 16x cycle time |
Step: High | Yes; 32x cycle time |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | |
— Burden of 2-wire transmitter, max. | 750 Ω |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.003 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 0.5 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.3 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Diagnostic messages |
Wire-break | Yes; Measuring range 1 to 5 V only |
Group error | Yes |
Overflow/underflow | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 7 byte |
Diagnostics wire break | 1 |
Measurement type/range | 1 |
Group diagnostics | 1 |
Overflow/underflow | 1 |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | No |
Isolation |
Isolation tested with | 500 V DC |
Standards, approvals, certificates |
CE mark | Yes |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/13/2019 |