| ***Spare part*** SIPLUS LOGO! 12/24RCo -40...+70°C with conformal coating based on 6ED1052-2MD00-0BA6 |
Installation type/mounting |
Mounting | on 35 mm DIN rail, 4 spacing units wide |
Supply voltage |
Rated value (DC) | |
12 V DC | Yes |
24 V DC | Yes |
permissible range, lower limit (DC) | 10.8 V; 11 V @ >55 °C |
permissible range, upper limit (DC) | 28.8 V; 27.5 V @ >55 °C |
Time of day |
Time switching clocks |
Number | 8 |
Power reserve | 80 h |
Digital inputs |
Number of digital inputs | 8; Of which 4 can be used in analog mode (0 to 10 V) |
Digital outputs |
Number of digital outputs | 4; Relays |
Short-circuit protection | No; external fusing necessary |
Relay outputs |
Switching capacity of contacts |
— with inductive load, max. | 3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s |
— with resistive load, max. | 10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s |
EMC |
Emission of radio interference acc. to EN 55 011 |
Limit class B, for use in residential areas | Yes |
Degree and class of protection |
Degree of protection acc. to EN 60529 | |
IP20 | Yes |
Standards, approvals, certificates |
CSA approval | No |
UL approval | Yes; File: E120869 // Tmax = 55 °C |
FM approval | No |
developed in accordance with IEC 61131 | Yes |
according to VDE 0631 | Yes |
Marine approval | No |
Ambient conditions |
Ambient temperature during operation |
min. | -40 °C; = Tmin |
max. | 70 °C; = Tmax; 55 °C @ UL/cUL use |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Conformal coating |
Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high availability |
Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
Dimensions |
Width | 72 mm |
Height | 90 mm |
Depth | 55 mm |
last modified: | 03/25/2019 |