6AG1052-2MD00-2BA6
SIPLUS LOGO! 12/24RCo

From SIEMENS

***Spare part*** SIPLUS LOGO! 12/24RCo -40...+70°C with conformal coating based on 6ED1052-2MD00-0BA6
Installation type/mounting
Mountingon 35 mm DIN rail, 4 spacing units wide
Supply voltage
Rated value (DC)
12 V DCYes
24 V DCYes
permissible range, lower limit (DC)10.8 V; 11 V @ >55 °C
permissible range, upper limit (DC)28.8 V; 27.5 V @ >55 °C
Time of day
Time switching clocks
Number8
Power reserve80 h
Digital inputs
Number of digital inputs8; Of which 4 can be used in analog mode (0 to 10 V)
Digital outputs
Number of digital outputs4; Relays
Short-circuit protectionNo; external fusing necessary
Relay outputs
Switching capacity of contacts
— with inductive load, max.3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s
— with resistive load, max.10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s
EMC
Emission of radio interference acc. to EN 55 011
Limit class B, for use in residential areasYes
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Standards, approvals, certificates
CSA approvalNo
UL approvalYes; File: E120869 // Tmax = 55 °C
FM approvalNo
developed in accordance with IEC 61131Yes
according to VDE 0631Yes
Marine approvalNo
Ambient conditions
Ambient temperature during operation
min.-40 °C; = Tmin
max.70 °C; = Tmax; 55 °C @ UL/cUL use
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high availability
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Dimensions
Width72 mm
Height90 mm
Depth55 mm
last modified:03/25/2019

External links