5SV4644-0
RCCB

From SIEMENS

Residual current operated circuit breaker, 4-pole, Type AC, In: 40 A, 300 mA, Un AC: 400 V
Model
Product brand nameSENTRON
Product designationRCCB
Design of the productInstantaneous
General technical data
Number of poles4
Size of installation devices / acc. to DIN 438801
Protection against electrical shockFinger and back-of-hand safe
Short-circuit current rating10 kA
circuit-breaker / Design5SV4
Mechanical service life (switching cycles) / typical10 000
Switching function / short-term delayedNo
Overvoltage categoryIII
Supply voltage
Supply voltage
at AC / rated value230/400 V
for testing equipment / minimum100 V
Supply voltage frequency
rated value50 Hz
Protection class
Protection class IPIP20, if the distribution board is installed, with connected conductors
Switching capacity
Switching capacity current / according to IEC 61008-1 / rated value0.8 kA
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole2 W
Electricity
Tripping residual current / rated value300 mA
Tripping residual / rated value / derated current
at 40 Cel40 A
at 45 Cel38.1 A
at 50 Cel35.59 A
at 55 Cel32.29 A
at 60 Cel28.19 A
at 65 Cel23.3 A
at 70 Cel17.62 A
Type of fault currentAC
Current / at AC / rated value40 A
I2t-value / permissible41 000 A²·s
Product details
Product feature / silicon-freeYes
Product extension / can be installed / supplementary devicesYes
Number
Number of test cycles / for environmental testing / acc. to IEC 60068-2-3028
Connections
Connectable conductor cross-section / stranded
minimum0.75 mm²
maximum35 mm²
Connectable conductor cross-section / solid
minimum0.75 mm²
maximum35 mm²
Tightening torque / with screw-type terminals
minimum2.5 N·m
maximum3 N·m
Position / of power supply cordtop or bottom
Mechanical Design
Height90 mm
Width72 mm
Depth70 mm
Mounting positionany
Installation depth70 mm
Number of width units4
Mounting typeDIN rail (REG)
Net weight350 g
Environmental conditions
Ambient temperature
minimum-25 °C
maximum45 °C
during storage / minimum permissible-40 °C
during storage / maximum permissible75 °C