5SU1624-0KK82 RCBO elm
From SIEMENS
RCBO, 10 kA, 2P, Type AC, 300 mA, B char., In: 125 A, Un AC: 230 V | ||
Model | ||
Product brand name | SENTRON | |
Product designation | RCBO | |
Design of the product | Instantaneous | |
General technical data | ||
Number of poles | 2 | |
Number of poles / Note | 2P | |
Number of poles / with protection | 2 | |
Tripping characteristic class | B | |
circuit-breaker / Design | 5SU1 | |
Mechanical service life (switching cycles) / typical | 10 000 | |
Overvoltage category | III | |
Voltage | ||
Surge current resistance / at (8/20) µs | 1 kA | |
Supply voltage | ||
Supply voltage | ||
for testing equipment / minimum | 100 V | |
Supply voltage frequency / rated value | 50 Hz | |
Protection class | ||
Protection class IP | IP20, if the distribution board is installed, with connected conductors | |
Energy limiting class | 3 | |
Switching capacity | ||
Switching capacity current | ||
acc. to EN 60898 / rated value | 10 kA | |
acc. to IEC 60947-2 / rated value | 10 kA | |
Rated residual switching capacity (IΔm) / according to IEC 61009-1 | 10 kA | |
Electricity | ||
Tripping residual current / rated value | 300 mA | |
Tripping residual / rated value / derated current | ||
at 30 Cel | 125 A | |
at 40 Cel | 115.62 A | |
at 45 Cel | 111.25 A | |
at 50 Cel | 106.25 A | |
at 55 Cel | 101.25 A | |
at 60 Cel | 96.25 A | |
Type of fault current | AC | |
Current / at AC / rated value | 125 A | |
Product details | ||
Product feature / Touch protection | Yes | |
Product feature | ||
halogen-free | Yes | |
silicon-free | Yes | |
Product function | ||
Product function / neutral conductor switching | Yes | |
Number | ||
Number of test cycles / for environmental testing / acc. to IEC 60068-2-30 | 28 | |
Connections | ||
Connectable conductor cross-section / stranded | ||
minimum | 6 mm² | |
maximum | 50 mm² | |
Connectable conductor cross-section | ||
solid | ||
— minimum | 6 mm² | |
— maximum | 50 mm² | |
finely stranded / with core end processing | ||
— minimum | 6 mm² | |
— maximum | 35 mm² | |
Tightening torque / with screw-type terminals | ||
minimum | 3 N·m | |
maximum | 3.5 N·m | |
Position / of power supply cord | Either top or bottom | |
Mechanical Design | ||
Mounting position | any | |
Installation depth | 70 mm | |
Number of width units | 2 | |
Net weight | 930 g | |
Environmental conditions | ||
Degree of pollution | 2 | |
Influence of the surrounding temperature | Max. 95% humidity | |
Ambient temperature | ||
minimum | -25 °C | |
maximum | 55 °C | |
during storage / minimum | -40 °C | |
during storage / maximum | 75 °C |