5SJ4145-6HG40
CIRCUIT BREAKER 14KA 1POL B45

From SIEMENS

Miniature circuit breaker 240 V 14kA, 1-pole, B, 45 A, D=70 mm according to UL 489, equal polarity
Model
Product brand nameSENTRON
Product designationMiniature circuit breakers
Design of the productMiniature circuit-breaker 5SJ4
General technical data
Number of poles1
Number of poles / Note1P
Tripping characteristic classB
Installation environment regarding EMCSuitable for environment B (immunity to interference not applicable)
circuit-breaker / Design5SJ4
Mechanical service life (switching cycles) / typical20 000
Reference code / acc. to DIN 40719 extended according to IEC 204-2 / acc. to IEC 750F
Overvoltage category3
Voltage
Type of voltageAC/DC
Insulation voltage / at AC / rated value440 V
Supply voltage
Supply voltage / at AC / rated value400 V
Supply voltage frequency / rated value50 Hz
Protection class
Protection class IPIP20, with connected conductors, IP 40 in the handle range
Switching capacity
Switching capacity current
acc. to EN 60898 / rated value10 kA
acc. to IEC 60947-2 / rated value15 kA
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole5.7 W
Electricity
Tripping residual / rated value / derated current / at 40 Cel45 A
Current / at AC / rated value45 A
Main circuit
Type of voltage supply / at AC / acc. to UL 489 and CSA C22.2 No. 5-02240/120
Operating voltage
at AC / acc. to UL 489 and CSA C22.2 No. 5-02 / maximum120 V
at DC / 1-channel / acc. to UL 489 and CSA C22.2 No. 5-02 / maximum60 V
at DC / rated value / maximum60 V
Suitability for operationMechanical engineering / industry
Product details
Product feature / Touch protectionYes
Product component
Tunnel terminals topNo
Tunnel terminals bottomNo
combined terminal topYes
combined terminal bottomYes
Product feature
halogen-freeYes
sealableYes
silicon-freeYes
Product extension / can be installed / supplementary devicesYes
Product function
Product function
NoteTerminal tightening torque for Cu, 60/75°C; 3.5Nm/31lb.in
neutral conductor switchingNo
Short circuit
Breaking capacity short-circuit current (Icn) / at AC / acc. to UL 1077 and CSA C22.2 No.23514 kA
Number
Number of test cycles / for environmental testing / acc. to IEC 60068-2-306
Connections
Connectable conductor cross-section / finely stranded / with core end processing
minimum1.5 mm²
maximum25 mm²
Position / of power supply cordAny
Mechanical Design
Height90 mm
Width18 mm
Depth70 mm
Mounting positionany
Installation depth70 mm
Number of width units1
Mounting typeon standard mounting rail
Net weight167 g
Environmental conditions
Degree of pollution3
Influence of the surrounding temperaturemax. 95% humidity
Vibration resistance50 m/s² at 25 to 150Hz and 60m/s² at 35Hz (4sec)
Vibration resistance / acc. to IEC 60068-2-650 m/s² at 25 to 150Hz and 60m/s² at 35Hz (4sec)
Ambient temperature
minimum-25 °C
maximum55 °C
during storage / minimum-40 °C
during storage / maximum75 °C

External links