4AU3696-0EU30-2XC0 AUTOTRANSFORMER; PHASES:3;
From SIEMENS
AUTOTRANSFORMER; PHASES:3; PN,D(KVA):63; UPRI(V):240-230-220-200; USEC(V):230; ISEC(A):158,1; F(HZ):50...60; VECTOR GR./SHIELD WNG.:YNA0 /0; TA/ISOKL:50 /H; IP23; TYPE OF TERMINALS:FLAT-TYPE TERMINAL; INSTALLATION:SCREW; EN 61558-2-13 >AUTOTRANSFORMER< | |||
General technical data | |||
Product designation | autotransformer | ||
Product brand name | SIDAC | ||
Operating apparent output rated value | V·A | 63 000 | |
Efficiency | 0.94 | ||
Connection method for transformers | YNa0 | ||
Certificate of suitability | CE | ||
Product function | |||
Temperature monitoring | No | ||
Insulation monitoring | No | ||
Short-circuit and overload proof | No | ||
Number of shielding windings | 0 | ||
Inputs | |||
Phase number of the inputs | 3 | ||
Input voltage | |||
_1 rated value | V | 240 | |
_2 rated value | V | 230 | |
_3 rated value | V | 220 | |
_4 rated value | V | 200 | |
Electrical input frequency | |||
minimum | Hz | 50 | |
maximum | Hz | 60 | |
Outputs | |||
Phase number of the outputs | 3 | ||
Output voltage | |||
_1 rated value | V | 230 | |
Electrical output frequency | |||
maximum | Hz | 60 | |
minimum | Hz | 50 | |
Ambient conditions | |||
Thermal class acc. to IEC 60085 | H | ||
Ambient temperature rated value | °C | 50 | |
Protection class IP | IP23 | ||
Mechanical data | |||
Type of electrical connection | |||
at output for main current circuit | flat connector | ||
at input for main current circuit | flat connector | ||
Mounting type | screws | ||
Construction form of the iron core | 3UI 180/75 | ||
Width | m | 0.46 | |
Height | m | 0.555 | |
Depth | m | 0.465 | |
Certificates/ approvals |