4AM5741-8BD40-0CN2
CONTROL CIRCUIT TRANSFORMER;

From SIEMENS

CONTROL CIRCUIT TRANSFORMER; PHASES:1; PN/PN(S6)(KVA):1 /5,01; UPRI(V):575-550-525-500- 480-460 -440-415-400-380-230-220-200- 190; USEC(V):230(2X115); ISEC(A):4,35-8,7; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:SCREW/TAB CONNECTION; INSTALLATION:SCREW; EN 61558-2-1, 2-2 >MAINS TRANSFORMER< >CONTROL CIRCUIT TRANSFORMER<
General technical data:
Product designationcontrol circuit transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A1 000
Efficiency0.93
Connection method for transformersIi0
Certificate of suitabilityCE / cRUus
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Short-term vector powerV·A5 010
Relative short-circuit voltage%2.657
Inputs:
Phase number of the inputs1
Input voltage
_1 rated valueV575
_2 rated valueV550
_3 rated valueV525
_4 rated valueV500
_5 rated valueV480
_6 rated valueV460
_7 rated valueV440
_8 rated valueV415
_9 rated valueV400
_10 rated valueV380
_11 rated valueV230
_12 rated valueV220
_13 rated valueV200
_14 rated valueV190
Electrical input frequency
minimumHz50
maximumHz60
Outputs:
Phase number of the outputs1
Output voltage
_1 rated valueV230
_2 rated valueV115
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions:
Thermal class acc. to IEC 60085B
Ambient temperature rated value°C40
Protection class IPIP00
Mechanical data:
Type of electrical connection
at output for main current circuitscrew-type terminals / tab terminals
at input for main current circuitscrew-type terminals / tab terminals
Mounting typescrews
Construction form of the iron coreEI 150/90
Widthm0.152
Heightm0.144
Depthm0.132