3VT3763-2AA56-0AA0
CIRCUIT BREAKER VT 630 N

From SIEMENS

circuit breaker 3VT3 standard breaking capacity Icu=36kA, 415V AC 4-pole; circuit breaker w/o Electronic Trip Unit N connected+measured without auxiliary release without auxiliary/alarm switch
Model
Product brand nameSENTRON
Product designation3VT1_5 molded case circuit breakers
Design of the operating mechanismtoggle handle
Type of the driving mechanism / motor driveNo
General technical data
Number of poles4
Size of the circuit-breaker3VT3
Electrical endurance (switching cycles) / typical5 000
Usage categoryA
Performance class for circuit breakerN
Mechanical service life (switching cycles) / typical20 000
Operating frequency / maximum120 1/h
Voltage
Insulation voltage / rated value690 V
Surge voltage resistance / rated value8 kV
Protection class
Protection class IPIP40
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole25 W
Electricity
Operating current / at 45 °C / rated value630 A
Continuous current / rated value630 A
Derating temperature / for the rated value of the continuous current55 °C
Main circuit
Operating frequency
1 / rated value50 Hz
2 / rated value60 Hz
Operating voltage
rated value / maximum690 V
for main current circuit / at AC / at 50 Hz / maximum690 V
for main current circuit / at AC / at 60 Hz / maximum690 V
for main current circuit / at DC / maximum440 V
Operating current
at 40 °C / rated value630 A
at 50 °C / rated value630 A
at 55 °C / rated value600 A
at 60 °C / rated value600 A
at 65 °C / rated value540 A
at 70 °C / rated value540 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Suitability
Suitability for useContact unit without release
Disconnecting meansYes
Product details
Product component
Trip indicatorNo
Auxiliary switchNo
Voltage triggerNo
undervoltage releaseNo
undervoltage release with leading contactNo
Product extension / optional / motor driveYes
Product function
Product function
Ground fault protectionNo
for neutral conductors / Short-circuit and overload proofNo
Phase failure detectionNo
Overload protectionNo
Short circuit
Operational short-circuit current breaking capacity (Ics)
at 240 V / rated value40 kA
at 415 V / rated value18 kA
at 500 V / rated value10 kA
at 690 V / rated value8 kA
Maximum short-circuit current breaking capacity (Icu)
at 240 V / rated value60 kA
at 415 V / rated value36 kA
at 500 V / rated value20 kA
at 690 V / rated value15 kA
Connections
Arrangement of electrical connectors / for main current circuitfront side
Type of electrical connection / for main current circuitscrew-type terminals
Mechanical Design
Height275 mm
Width185 mm
Depth117 mm
Mounting positionwith vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back
Mounting typefixed mounting
Net weight5.97 kg
Environmental conditions
Ambient temperature
during operation / minimum-40 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum70 °C