| circuit breaker 3VT3 standard breaking capacity Icu=36kA, 415V AC 4-pole; circuit breaker w/o Electronic Trip Unit N connected+measured without auxiliary release without auxiliary/alarm switch |
Model |
Product brand name | SENTRON |
Product designation | 3VT1_5 molded case circuit breakers |
Design of the operating mechanism | toggle handle |
Type of the driving mechanism / motor drive | No |
General technical data |
Number of poles | 4 |
Size of the circuit-breaker | 3VT3 |
Electrical endurance (switching cycles) / typical | 5 000 |
Usage category | A |
Performance class for circuit breaker | N |
Mechanical service life (switching cycles) / typical | 20 000 |
Operating frequency / maximum | 120 1/h |
Voltage |
Insulation voltage / rated value | 690 V |
Surge voltage resistance / rated value | 8 kV |
Protection class |
Protection class IP | IP40 |
Dissipation |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 25 W |
Electricity |
Operating current / at 45 °C / rated value | 630 A |
Continuous current / rated value | 630 A |
Derating temperature / for the rated value of the continuous current | 55 °C |
Main circuit |
Operating frequency | |
1 / rated value | 50 Hz |
2 / rated value | 60 Hz |
Operating voltage | |
rated value / maximum | 690 V |
for main current circuit / at AC / at 50 Hz / maximum | 690 V |
for main current circuit / at AC / at 60 Hz / maximum | 690 V |
for main current circuit / at DC / maximum | 440 V |
Operating current | |
at 40 °C / rated value | 630 A |
at 50 °C / rated value | 630 A |
at 55 °C / rated value | 600 A |
at 60 °C / rated value | 600 A |
at 65 °C / rated value | 540 A |
at 70 °C / rated value | 540 A |
Auxiliary circuit |
Number of CO contacts / for auxiliary contacts | 0 |
Number of NC contacts / for auxiliary contacts | 0 |
Number of NO contacts / for auxiliary contacts | 0 |
Suitability |
Suitability for use | Contact unit without release |
Disconnecting means | Yes |
Product details |
Product component | |
Trip indicator | No |
Auxiliary switch | No |
Voltage trigger | No |
undervoltage release | No |
undervoltage release with leading contact | No |
Product extension / optional / motor drive | Yes |
Product function |
Product function | |
Ground fault protection | No |
for neutral conductors / Short-circuit and overload proof | No |
Phase failure detection | No |
Overload protection | No |
Short circuit |
Operational short-circuit current breaking capacity (Ics) | |
at 240 V / rated value | 40 kA |
at 415 V / rated value | 18 kA |
at 500 V / rated value | 10 kA |
at 690 V / rated value | 8 kA |
Maximum short-circuit current breaking capacity (Icu) | |
at 240 V / rated value | 60 kA |
at 415 V / rated value | 36 kA |
at 500 V / rated value | 20 kA |
at 690 V / rated value | 15 kA |
Connections |
Arrangement of electrical connectors / for main current circuit | front side |
Type of electrical connection / for main current circuit | screw-type terminals |
Mechanical Design |
Height | 275 mm |
Width | 185 mm |
Depth | 117 mm |
Mounting position | with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back |
Mounting type | fixed mounting |
Net weight | 5.97 kg |
Environmental conditions |
Ambient temperature | |
during operation / minimum | -40 °C |
during operation / maximum | 70 °C |
during storage / minimum | -40 °C |
during storage / maximum | 70 °C |