3VL9400-3MQ00 ACCESSORY F. VL400, MOT.OP.MECH. W. SES
From SIEMENS
accessory for VL400, mot. op. mech. w/ strd en. mech 220...250V AC/DC | ||
Model | ||
Product brand name | SENTRON | |
Product designation | Motorized operating mechanism with stored energy mechanism | |
Type of the driving mechanism | Motorized operating mechanism with spring energy store | |
General technical data | ||
Break time / typical | 5 s | |
Pulse duration / minimum | 50 ms | |
Operating frequency / maximum | 120 1/h | |
Voltage | ||
Fuse protection type / for external auxiliary power supply / required | NEOZED fuse (gL/gG): 2 A / miniature circuit breaker, C char.: 2 A | |
Operating range factor control supply voltage rated value | ||
at AC / at 60 Hz / initial value | 0.85 | |
at AC / at 60 Hz / Full-scale value | 1.1 | |
at DC / initial value | 0.85 | |
at DC / Full-scale value | 1.1 | |
Protection class | ||
Protection class IP | IP30 | |
Electricity | ||
Make time / typical | 0.1 s | |
Control current | ||
Operating apparent output | 200 V·A | |
Control supply voltage | ||
at DC / rated value / minimum | 250 V | |
at DC / rated value / maximum | 220 V | |
at AC / at 50 Hz / rated value / minimum | 220 V | |
at AC / at 50 Hz / rated value / maximum | 250 V | |
at AC / at 60 Hz / rated value / minimum | 220 V | |
at AC / at 60 Hz / rated value / maximum | 250 V | |
Operating range factor control supply voltage rated value / at AC / at 50 Hz | ||
initial value | 0.85 | |
Full-scale value | 1.1 | |
Accessories | ||
accessories | Accessories for VL400 | |
Connections | ||
Connectable conductor cross-section / stranded | ||
minimum | 0.75 mm² | |
maximum | 1.5 mm² | |
Wire stripping length | 10 mm | |
Connectable conductor cross-section | ||
solid | ||
— minimum | 0.75 mm² | |
— maximum | 1.5 mm² | |
finely stranded / with core end processing | ||
— minimum | 0.75 mm² | |
— maximum | 1.5 mm² | |
Tightening torque | ||
maximum | 1 N·m | |
Mechanical Design | ||
Height | 160 mm | |
Width | 140 mm | |
Depth | 160 mm | |
Net weight | 4 593 g | |
Environmental conditions | ||
Ambient temperature | ||
during operation / minimum | -25 °C | |
during operation / maximum | 70 °C | |
during storage / minimum | -40 °C | |
during storage / maximum | 80 °C |