| circuit breaker 3VA2 IEC frame 630 breaking capacity class C Icu=110kA @ 415V 3-pole, motor protection ETU350M, LSI, In=500A overload protection Ir=200A...500A short-circuit protection Isd=3...15 x Ir, Ii=15 x In nut keeper kit |
Model |
Product brand name | SENTRON |
Product designation | Molded case circuit breaker |
Product version | Motor protection |
Design of the overcurrent release | ETU350M |
Protective function of the overcurrent release | LSI |
Number of poles | 3 |
General technical data |
Rated insulation voltage Ui | 800 V |
Max. rated operational voltage Ue with AC 50/60Hz | 690 V |
Power loss [W] / maximum | 99 W |
Active power loss / for rated value of the current / at AC / in hot operating state / per pole | 33 W |
Latching - endurance | 15 000 |
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz | 4 000 |
Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz | 4 000 |
Electrical endurance (switching cycles) / at AC-3 / at 380/415 V 50/60 Hz | 2 500 |
Neutral conductors / upgradeable/retrofittable | No |
Ground fault monitoring version | Without |
Product function | |
communication function | No |
Phase failure detection | Yes |
other measurement function | No |
Net weight | 4.3 kg |
Electricity |
Max. rated operational voltage of the size of the circuit-breaker | 630 A |
Rated continuous current Iu | 500 A |
Operating current | |
at 40 °C | 500 A |
at 45 °C | 500 A |
at 50 °C | 500 A |
at 55 °C | 495 A |
at 60 °C | 490 A |
at 65 °C | 485 A |
at 70 °C | 480 A |
Switching capacity according to IEC 60947 |
Switching capacity class of the circuit breaker | C |
Maximum short-circuit current breaking capacity (Icu) | |
at 240 V | 150 kA |
at 415 V | 110 kA |
at 440 V | 110 kA |
at 690 V | 9 kA |
Operational short-circuit current breaking capacity (Ics) | |
at 240 V | 150 kA |
at 415 V | 110 kA |
at 440 V | 110 kA |
at 690 V | 9 kA |
Short-circuit current making capacity (Icm) | |
at 240 V | 330 kA |
at 415 V | 242 kA |
at 440 V | 242 kA |
at 690 V | 15.3 kA |
Adjustable parameters |
Adjustable response value current / lr min. | 200 A |
Adjustable response value current / Ir max. | 500 A |
Adjustable response value time / tr min. | 4 |
Adjustable response value time / tr max. | 15 |
Adjustable response value current / Isd min. | 1 500 A |
Adjustable response value current / Isd max. | 7 500 A |
Short-term delayed / tripping switchable / I2t=ON/OFF | No |
Adjustable response value time / tsd min. | 0.03 s |
Adjustable response value time / tsd max. | 0.03 s |
Adjustable response value time / tsd min. | 0 s |
Adjustable response value time / tsd max. | 0 s |
Adjustable response value current / li min. | 7 500 A |
Adjustable response value current / li max. | 7 500 A |
Ground fault protection / tripping switchable / I2t=ON/OFF | No |
Mechanical Design |
Height [in] | 9.8 in |
Height | 248 mm |
Width [in] | 5.4 in |
Width | 138 mm |
Depth [in] | 4.3 in |
Depth | 110 mm |
Connections |
Arrangement of electrical connectors / for main current circuit | Front terminal |
Type of electrical connection / for main current circuit | Lug terminal |
Type of connectable conductor cross-section, connection screw, width x thickness , min. | 20 x 1 |
Type of connectable conductor cross-section, connection screw, width x thickness , max. | 35 x 10 |
Auxiliary circuit |
Number of CO contacts / for auxiliary contacts | 0 |
Accessories |
Product extension / optional / motor drive | Yes |
Environmental conditions |
Protection class IP / on the front | IP40 |
Ambient temperature | |
during operation / minimum | -25 °C |
during operation / maximum | 70 °C |
during storage / minimum | -40 °C |
during storage / maximum | 80 °C |