3VA1225-1AA32-0AA0
SD_IEC_FS250_250A_3P

From SIEMENS

switch disconnector 3VA1 IEC frame 250 3-pole SD100, In=250A without overload protection w/o short-circuit protection nut keeper kit
Model
Product brand nameSENTRON
Product designationSwitch disconnector
Product versionin MCCB design
Number of poles3
Design of the auxiliary releasewithout
Auxiliary contact versionWithout
General technical data
Rated insulation voltage Ui800 V
Max. rated operational voltage Ue with AC 50/60Hz690 V
Max. rated operational voltage Ue with DC500 V
Power loss [W] / maximum57 W
Latching - endurance15 000
Product function
communication functionNo
Electricity
Rated continuous current Iu250 A
Short-time current resistance (Icw)
limited to 1 s3 kA
Mechanical Design
Height158 mm
Width105 mm
Depth70 mm
Connections
Arrangement of electrical connectors / for main current circuitFront terminal
Type of electrical connection / for main current circuitbusbar connection
Auxiliary circuit
Product component
undervoltage releaseNo
Voltage triggerNo
undervoltage release with leading contactNo
Trip indicatorNo
Number of CO contacts / for auxiliary contacts0
Accessories
Product extension / optional / motor driveYes
Environmental conditions
Protection class IP / on the frontIP40
Ambient temperature
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum80 °C

External links