3TH2262-1AG1
CONTACTOR RELAY 62E EN 50 011

From SIEMENS

Contactor relay 62 E EN 50 011 6 NO+2 NC, Flat connector terminal Overall width 45 mm Alternating current operation 110 V AC 60 Hz/92 V AC 50 Hz !!! Phased-out product !!! Successor is SIRIUS 3RH21
Product designationAuxiliary contactor
Product type designation3TH2
Size of contactor0
Protection class IP on the frontIP20
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference code acc. to DIN EN 81346-2K
Reference code acc. to DIN EN 61346-2K
Type of voltage of the control supply voltageAC
Control supply voltage at AC
at 50 Hz rated value92 V
at 60 Hz rated value110 V
Control supply voltage frequency
1 rated value50 Hz
2 rated value60 Hz
Number of NC contacts for auxiliary contacts2
delayed switching0
lagging switching0
make-before-break switching0
Number of NO contacts for auxiliary contacts6
delayed switching0
leading contact0
make-before-break switching0
Number of CO contacts for auxiliary contacts0
Identification number and letter for switching elements62 E
Operating current at AC-15
at 230 V rated value4 A
at 400 V rated value3 A
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Height48 mm
Width45 mm
Depth96 mm
Type of electrical connection for auxiliary and control current circuittab terminals 2x 2.8 mm
B10 value with high demand rate acc. to SN 31920400 000; With 0.3 x Ie
T1 value for proof test interval or service life acc. to IEC 6150820 y
Protection against electrical shockfinger-safe

External links