| Contact block for position switch 3SE51/52 1 NO/1 NC quick action contact 2 x 2 mm contact clearance |
Product brand name | SIRIUS |
Product designation | contact |
Product type designation | 3SE5 |
General technical data |
Product function | |
positive opening | Yes |
Insulation voltage | |
rated value | 400 V |
Degree of pollution | class 3 |
Surge voltage resistance rated value | 6 kV |
Protection class IP | IP00 |
Shock resistance | |
acc. to IEC 60068-2-27 | 30 g / 11 ms |
Vibration resistance | |
acc. to IEC 60068-2-6 | 0.35 mm/5g |
Mechanical service life (switching cycles) | |
typical | 15 000 000 |
Electrical endurance (switching cycles) | |
at AC-15 at 230 V typical | 100 000 |
Electrical endurance (switching cycles) with contactor 3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025, 3RT1026 typical | 10 000 000 |
Electrical operating cycles in one hour with contactor 3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025, 3RT1026 | 6 000 |
Thermal current | 10 A |
Continuous current of the C characteristic MCB | 1 A; for a short-circuit current smaller than 400 A |
Continuous current of the quick DIAZED fuse link | 10 A; for a short-circuit current smaller than 400 A |
Continuous current of the DIAZED fuse link gG | 6 A |
Active principle | mechanical |
Repeat accuracy | 0.1 mm |
Width of the sensor | 25 mm |
Operating frequency rated value | 50 ... 60 Hz |
Number of NC contacts for auxiliary contacts | 1 |
Number of NO contacts for auxiliary contacts | 1 |
Number of CO contacts for auxiliary contacts | 1 |
Operating current at AC-15 | |
at 24 V rated value | 6 A |
at 125 V rated value | 6 A |
at 240 V rated value | 6 A |
at 400 V rated value | 4 A |
Operating current at DC-13 | |
at 24 V rated value | 3 A |
at 125 V rated value | 0.55 A |
at 250 V rated value | 0.27 A |
at 400 V rated value | 0.12 A |
Design of the interface for safety-related communication | without |
Enclosure |
Coating of the enclosure | Other types |
Drive Head |
Design of the switching function | positive opening, 2x2 mm contact opening |
Circuit principle | snap-action contacts |
Number of switching contacts safety-related | 1 |
Connections/Terminals |
Type of electrical connection | screw-type terminals |
Type of connectable conductor cross-sections | |
solid | 1x (0.5 ... 1.5 mm²), 2x (0.5 ... 0.75 mm²) |
finely stranded with core end processing | 1x (0.5 ... 1.5 mm²), 2x (0.5 ... 0.75 mm²) |
at AWG conductors solid | 1x (20 ... 16), 2x (20 ... 18) |
at AWG conductors stranded | 1x (20 ... 16), 2x (20 ... 18) |
Communication/ Protocol |
Design of the interface | without |
Ambient conditions |
Ambient temperature | |
during operation | -25 ... +85 °C |
during storage | -40 ... +90 °C |
Explosion protection category for dust | none |
Installation/ mounting/ dimensions |
Mounting position | any |
Mounting type | snap-on mounting |