| SIRIUS soft starter with brake function integrated in motor, IP54 29 A, 15 kW/400 V, 40 °C 400-575 V AC, 24 V DC plug-in connection Multi-unit packaging for SD in mesh box |
General technical data |
Product brand name | | SIRIUS |
Product feature | | |
integrated bypass contact system | | Yes |
Thyristors | | Yes |
Product function | | |
motor overload protection | | No |
Evaluation of thermistor motor protection | | Yes |
inside-delta circuit | | No |
Reference code acc. to DIN EN 61346-2 | | Q |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | | G |
Power Electronics |
Product designation | | soft starters for standard applications |
Operating current | | |
at 40 °C rated value | A | 29 |
Mechanical power output for three-phase motors | | |
at 400 V | | |
— at standard circuit at 40 °C rated value | W | 15 000 |
at 500 V | | |
— at standard circuit at 40 °C rated value | W | 18 500 |
Operating frequency rated value | Hz | 50 ... 60 |
Relative negative tolerance of the operating frequency | % | -10 |
Relative positive tolerance of the operating frequency | % | 10 |
Operating voltage at standard circuit rated value | V | 400 ... 575 |
Minimum load [%] | % | 15 |
Continuous operating current [% of Ie] at 40 °C | % | 115 |
Power loss [W] at operating current at 40 °C during operation typical | W | 21 |
Control electronics |
Type of voltage of the control supply voltage | | AC/DC |
Control supply voltage 1 at AC | | |
at 50 Hz rated value | V | 24 |
at 60 Hz rated value | V | 24 |
Control supply voltage 1 at DC rated value | V | 24 |
Mechanical data |
Width | mm | 252 |
Height | mm | 187 |
Depth | mm | 85 |
Mounting type | | direct mounting |
Number of poles for main current circuit | | 3 |
Connections/Terminals |
Type of electrical connection | | |
for main current circuit | | tab connection |
for auxiliary and control current circuit | | tab connection |
Number of NC contacts for auxiliary contacts | | 3 |
Number of NO contacts for auxiliary contacts | | 1 |
Number of CO contacts for auxiliary contacts | | 0 |
Ambient conditions |
Installation altitude at height above sea level | m | 2 000 |
Ambient temperature | | |
during operation | °C | -25 ... +40 |
during storage | °C | -25 ... +80 |
Derating temperature | °C | 40 |