3RV2011-1EA15-0BA0
SPECIAL TYPE CIRCUIT BREAKER 4A

From SIEMENS

Special type Circuit breaker size S00 for motor protection, CLASS 10 A-release 2.8...4 A N release 52 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC Ambient temperature -50 °C 500 switching cycles
Product brand nameSIRIUS
Product designationCircuit breaker
Design of the productFor motor protection
Product type designation3RV2
General technical data
Size of the circuit-breakerS00
Size of contactor can be combined company-specificS00, S0
Product extension
Auxiliary switchYes
Power loss [W] total typical6 W
Insulation voltage with degree of pollution 3 rated value690 V
Surge voltage resistance rated value6 kV
maximum permissible voltage for safe isolation
in networks with grounded star point between main and auxiliary circuit400 V
in networks with grounded star point between main and auxiliary circuit400 V
Protection class IP
on the frontIP20
of the terminalIP20
Shock resistance
acc. to IEC 60068-2-2725g / 11 ms
Mechanical service life (switching cycles)
of the main contacts typical500
of auxiliary contacts typical500
Electrical endurance (switching cycles)
typical500
Type of protectionIncreased safety
Certificate of suitability ATEXNo
Protection against electrical shockfinger-safe when touched vertically from front acc. to IEC 60529
Reference code acc. to DIN EN 81346-2Q
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Temperature compensation-20 ... +60 °C
Relative humidity during operation10 ... 95 %
Main circuit
Number of poles for main current circuit3
Adjustable pick-up value current of the current-dependent overload release2.8 ... 4 A
Operating voltage
rated value690 V
at AC-3 rated value maximum690 V
Operating frequency rated value50 ... 60 Hz
Operating current rated value4 A
Operating current
at AC-3
— at 400 V rated value4 A
Operating power
at AC-3
— at 230 V rated value750 W
— at 400 V rated value1 500 W
— at 500 V rated value2 200 W
— at 690 V rated value3 000 W
Operating frequency
at AC-3 maximum15 1/h
Auxiliary circuit
Design of the auxiliary switchtransverse
Number of NC contacts for auxiliary contacts1
Number of NO contacts for auxiliary contacts1
Number of CO contacts
for auxiliary contacts0
Operating current of auxiliary contacts at AC-15
at 24 V2 A
at 120 V0.5 A
at 125 V0.5 A
at 230 V0.5 A
Operating current of auxiliary contacts at DC-13
at 24 V1 A
at 60 V0.15 A
Protective and monitoring functions
Product function
Ground fault detectionNo
Phase failure detectionYes
Trip classCLASS 10
Design of the overload releasethermal
Operational short-circuit current breaking capacity (Ics) at AC
at 240 V rated value100 kA
at 400 V rated value100 kA
at 500 V rated value100 kA
at 690 V rated value4 kA
Maximum short-circuit current breaking capacity (Icu)
at AC at 240 V rated value100 kA
at AC at 400 V rated value100 kA
at AC at 500 V rated value100 kA
at AC at 690 V rated value6 kA
Breaking capacity short-circuit current (Icn)
at 1 current path at DC at 150 V rated value10 kA
with 2 current paths in series at DC at 300 V rated value10 kA
with 3 current paths in series at DC at 450 V rated value10 kA
Response value current
of instantaneous short-circuit trip unit52 A
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
at 480 V rated value4 A
at 600 V rated value4 A
Yielded mechanical performance [hp]
for single-phase AC motor
— at 110/120 V rated value0.125 hp
— at 230 V rated value0.333 hp
for three-phase AC motor
— at 200/208 V rated value0.75 hp
— at 220/230 V rated value0.75 hp
— at 460/480 V rated value2 hp
— at 575/600 V rated value3 hp
Contact rating of auxiliary contacts according to ULC300 / R300
Short-circuit protection
Product function Short circuit protectionYes
Design of the short-circuit tripmagnetic
Design of the fuse link
for short-circuit protection of the auxiliary switch requiredfuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)
Design of the fuse link for IT network for short-circuit protection of the main circuit
at 400 VgG 32 A
at 500 VgG 32 A
at 690 VgG 25 A
Installation/ mounting/ dimensions
Mounting positionany
(mounting type)screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Height97 mm
Width45 mm
Depth97 mm
Required spacing
with side-by-side mounting
— forwards0 mm
— Backwards0 mm
— upwards50 mm
— downwards50 mm
— at the side0 mm
for grounded parts
— forwards0 mm
— Backwards0 mm
— upwards50 mm
— at the side30 mm
— downwards50 mm
for live parts
— forwards0 mm
— Backwards0 mm
— upwards50 mm
— downwards50 mm
— at the side30 mm
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitNo
Type of electrical connection
for main current circuitscrew-type terminals
for auxiliary and control current circuitscrew-type terminals
Arrangement of electrical connectors for main current circuitTop and bottom
Type of connectable conductor cross-sections
for main contacts
— single or multi-stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
at AWG conductors for main contacts2x (18 ... 14), 2x 12
Type of connectable conductor cross-sections
for auxiliary contacts
— single or multi-stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
at AWG conductors for auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
Tightening torque
for main contacts with screw-type terminals0.8 ... 1.2 N·m
for auxiliary contacts with screw-type terminals0.8 ... 1.2 N·m
Design of screwdriver shaftDiameter 5 to 6 mm
Size of the screwdriver tipPozidriv 2
Design of the thread of the connection screw
for main contactsM3
of the auxiliary and control contactsM3
Safety related data
Proportion of dangerous failures
with low demand rate acc. to SN 3192050 %
with high demand rate acc. to SN 3192050 %
Failure rate [FIT]
with low demand rate acc. to SN 3192050 FIT
T1 value for proof test interval or service life acc. to IEC 6150810 y
Display version
for switching statusHandle

External links