3RV1821-1FD10
CIRCUIT-BREAKER, SIZE S0,

From SIEMENS

CIRCUIT-BREAKER, SIZE S0, FOR THE TRANSFORMER PROTECTION, WITH APPROBATION CIRC.-BREAKER UL 489, CSA C22.2 NO.5-02, A-TRIGGER 5 A, N-TRIGGER 104 A, SCREW CONNECTION, STANDARD BREAKING CAPACITY
Product brand nameSIRIUS
Product designationcircuit breaker
Design of the productfor transformer protection according to UL 489/CSA C22.2 No.5-02
General technical data
Product extension
Auxiliary switchYes
Power loss [W] total typical6 W
Surge voltage resistance rated value6 000 V
Protection class IP
on the frontIP20
Shock resistance25g / 11 ms
Mechanical service life (switching cycles)
of the main contacts typical100 000
Continuous current rated value5 A
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-20 ... +60 °C
during storage-50 ... +80 °C
during transport-50 ... +80 °C
Main circuit
Number of poles for main current circuit3
Adjustable pick-up value current of the current-dependent overload release5 ... 5 A
Operating voltage
rated value690 V
at AC-3 rated value maximum690 V
Operating current
at AC-3
— at 400 V rated value5 A
Operating frequency
at AC-3 maximum15 1/h
Auxiliary circuit
Number of CO contacts
for auxiliary contacts0
Protective and monitoring functions
Product function
Ground fault detectionNo
Phase failure detectionNo
Maximum short-circuit current breaking capacity (Icu)
at AC at 240 V rated value100 kA
at AC at 400 V rated value100 kA
at AC at 500 V rated value100 kA
at AC at 690 V rated value6 kA
at 480 AC Y/277 V acc. to UL 489 rated value50 kA
Short-circuit protection
Design of the overcurrent release and short-circuit releasethermomagnetic
Installation/ mounting/ dimensions
Mounting positionany
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Height144 mm
Width45 mm
Depth96 mm
Required spacing
with side-by-side mounting
— Backwards0 mm
— at the side0 mm
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitNo
Type of electrical connection
for main current circuitscrew-type terminals
for auxiliary and control current circuitscrew-type terminals
Arrangement of electrical connectors for main current circuitfront side
Type of connectable conductor cross-sections
for main contacts
— solid2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
— stranded2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
— finely stranded with core end processing2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
at AWG conductors for main contacts2x (14 ... 10)

External links