| Power contactor, AC-3 400 A, 200 kW / 400 V AC (50-60 Hz) / DC operation 220-240 V UC Auxiliary contacts 2 NO + 2 NC 3-pole, Size S12 Busbar connections Drive: conventional screw terminal |
Product brand name | SIRIUS |
Product designation | Power contactor |
Product type designation | 3RT1 |
General technical data |
Size of contactor | S12 |
Product extension | |
function module for communication | No |
Auxiliary switch | Yes |
Surge voltage resistance | |
of main circuit rated value | 8 kV |
of auxiliary circuit rated value | 6 kV |
maximum permissible voltage for safe isolation | |
between coil and main contacts acc. to EN 60947-1 | 690 V |
Protection class IP | |
on the front | IP00; IP20 on the front with cover / box terminal |
of the terminal | IP00 |
Shock resistance at rectangular impulse | |
at AC | 8,5g / 5 ms, 4,2g / 10 ms |
at DC | 8,5g / 5 ms, 4,2g / 10 ms |
Shock resistance with sine pulse | |
at AC | 13,4g / 5 ms, 6,5g / 10 ms |
at DC | 13,4g / 5 ms, 6,5g / 10 ms |
Mechanical service life (switching cycles) | |
of contactor typical | 10 000 000 |
of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
of the contactor with added auxiliary switch block typical | 10 000 000 |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | K |
Reference code acc. to DIN EN 81346-2 | Q |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -25 ... +60 °C |
during storage | -55 ... +80 °C |
Main circuit |
Number of poles for main current circuit | 3 |
Number of NO contacts for main contacts | 3 |
Operating voltage | |
at AC-3 rated value maximum | 1 000 V |
Operating current | |
at AC-1 at 400 V | |
— at ambient temperature 40 °C rated value | 430 A |
at AC-1 | |
— up to 690 V at ambient temperature 40 °C rated value | 430 A |
— up to 690 V at ambient temperature 60 °C rated value | 400 A |
— up to 1000 V at ambient temperature 40 °C rated value | 200 A |
— up to 1000 V at ambient temperature 60 °C rated value | 200 A |
at AC-2 at 400 V rated value | 400 A |
at AC-3 | |
— at 400 V rated value | 400 A |
— at 500 V rated value | 400 A |
— at 690 V rated value | 400 A |
— at 1000 V rated value | 180 A |
at AC-4 at 400 V rated value | 350 A |
at AC-5a up to 690 V rated value | 378 A |
at AC-5b up to 400 V rated value | 332 A |
at AC-6a | |
— up to 230 V at current peak n=20 rated value | 377 A |
— up to 400 V at current peak n=20 rated value | 377 A |
— up to 500 V at current peak n=20 rated value | 377 A |
— up to 690 V at current peak n=20 rated value | 377 A |
— up to 1000 V at current peak n=20 rated value | 180 A |
at AC-6a | |
— up to 230 V at current peak n=30 rated value | 251 A |
— up to 400 V at current peak n=30 rated value | 251 A |
— up to 500 V at current peak n=30 rated value | 251 A |
— up to 690 V at current peak n=30 rated value | 251 A |
— up to 1000 V at current peak n=30 rated value | 180 A |
Connectable conductor cross-section in main circuit at AC-1 | |
at 60 °C minimum permissible | 240 mm² |
at 40 °C minimum permissible | 300 mm² |
Operating current for approx. 200000 operating cycles at AC-4 | |
at 400 V rated value | 150 A |
at 690 V rated value | 135 A |
Operating current | |
at 1 current path at DC-1 | |
— at 24 V rated value | 400 A |
— at 110 V rated value | 33 A |
— at 220 V rated value | 3.8 A |
— at 440 V rated value | 0.9 A |
— at 600 V rated value | 0.6 A |
with 2 current paths in series at DC-1 | |
— at 24 V rated value | 400 A |
— at 110 V rated value | 400 A |
— at 220 V rated value | 400 A |
— at 440 V rated value | 4 A |
— at 600 V rated value | 2 A |
with 3 current paths in series at DC-1 | |
— at 24 V rated value | 400 A |
— at 110 V rated value | 400 A |
— at 220 V rated value | 400 A |
— at 440 V rated value | 11 A |
— at 600 V rated value | 5.2 A |
Operating current | |
at 1 current path at DC-3 at DC-5 | |
— at 24 V rated value | 400 A |
— at 110 V rated value | 3 A |
— at 220 V rated value | 0.6 A |
— at 440 V rated value | 0.18 A |
— at 600 V rated value | 0.125 A |
with 2 current paths in series at DC-3 at DC-5 | |
— at 24 V rated value | 400 A |
— at 110 V rated value | 400 A |
— at 220 V rated value | 2.5 A |
— at 440 V rated value | 0.65 A |
— at 600 V rated value | 0.37 A |
with 3 current paths in series at DC-3 at DC-5 | |
— at 24 V rated value | 400 A |
— at 110 V rated value | 400 A |
— at 220 V rated value | 400 A |
— at 440 V rated value | 1.4 A |
— at 600 V rated value | 0.75 A |
Operating power | |
at AC-1 | |
— at 230 V at 60 °C rated value | 151 kW |
— at 400 V rated value | 263 kW |
— at 400 V at 60 °C rated value | 263 kW |
— at 690 V rated value | 454 kW |
— at 690 V at 60 °C rated value | 454 kW |
— at 1000 V at 60 °C rated value | 329 kW |
at AC-2 at 400 V rated value | 200 kW |
at AC-3 | |
— at 230 V rated value | 132 kW |
— at 400 V rated value | 200 kW |
— at 500 V rated value | 250 kW |
— at 690 V rated value | 400 kW |
— at 1000 V rated value | 250 kW |
Operating power for approx. 200000 operating cycles at AC-4 | |
at 400 V rated value | 85 kW |
at 690 V rated value | 133 kW |
Thermal short-time current limited to 10 s | 3 200 A |
Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor | 35 W |
No-load switching frequency | |
at AC | 2 000 1/h |
at DC | 2 000 1/h |
Operating frequency | |
at AC-1 maximum | 700 1/h |
at AC-2 maximum | 200 1/h |
at AC-3 maximum | 500 1/h |
at AC-4 maximum | 130 1/h |
Control circuit/ Control |
Type of voltage of the control supply voltage | AC/DC |
Control supply voltage at AC | |
at 50 Hz rated value | 220 ... 240 V |
at 60 Hz rated value | 220 ... 240 V |
Control supply voltage at DC | |
rated value | 220 ... 240 V |
Operating range factor control supply voltage rated value of magnet coil at DC | |
initial value | 0.8 |
Full-scale value | 1.1 |
Operating range factor control supply voltage rated value of magnet coil at AC | |
at 50 Hz | 0.8 ... 1.1 |
at 60 Hz | 0.8 ... 1.1 |
Design of the surge suppressor | with varistor |
Apparent pick-up power of magnet coil at AC | |
at 50 Hz | 830 V·A |
Inductive power factor with closing power of the coil | |
at 50 Hz | 0.9 |
Apparent holding power of magnet coil at AC | |
at 50 Hz | 9.2 V·A |
Inductive power factor with the holding power of the coil | |
at 50 Hz | 0.9 |
Closing power of magnet coil at DC | 920 W |
Holding power of magnet coil at DC | 10 W |
Closing delay | |
at AC | 45 ... 100 ms |
at DC | 45 ... 100 ms |
Opening delay | |
at AC | 60 ... 100 ms |
at DC | 60 ... 100 ms |
Arcing time | 10 ... 15 ms |
Control version of the switch operating mechanism | Standard A1 - A2 |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | |
instantaneous contact | 2 |
Number of NO contacts for auxiliary contacts | |
instantaneous contact | 2 |
Operating current at AC-12 maximum | 10 A |
Operating current at AC-15 | |
at 230 V rated value | 6 A |
at 400 V rated value | 3 A |
at 500 V rated value | 2 A |
at 690 V rated value | 1 A |
Operating current at DC-12 | |
at 24 V rated value | 10 A |
at 48 V rated value | 6 A |
at 60 V rated value | 6 A |
at 110 V rated value | 3 A |
at 125 V rated value | 2 A |
at 220 V rated value | 1 A |
at 600 V rated value | 0.15 A |
Operating current at DC-13 | |
at 24 V rated value | 10 A |
at 48 V rated value | 2 A |
at 60 V rated value | 2 A |
at 110 V rated value | 1 A |
at 125 V rated value | 0.9 A |
at 220 V rated value | 0.3 A |
at 600 V rated value | 0.1 A |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
UL/CSA ratings |
Full-load current (FLA) for three-phase AC motor | |
at 480 V rated value | 361 A |
at 600 V rated value | 382 A |
Yielded mechanical performance [hp] | |
for three-phase AC motor | |
— at 200/208 V rated value | 125 hp |
— at 220/230 V rated value | 150 hp |
— at 460/480 V rated value | 300 hp |
— at 575/600 V rated value | 400 hp |
Contact rating of auxiliary contacts according to UL | A600 / Q600 |
Short-circuit protection |
Design of the fuse link | |
for short-circuit protection of the main circuit | |
— with type of coordination 1 required | gG: 630 A (690 V, 100 kA) |
— with type of assignment 2 required | gG: 500 A (690 V, 100 kA), aM: 400 A (690 V, 50 kA), BS88: 450 A (415 V, 50 kA) |
for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
Installation/ mounting/ dimensions |
Mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
Mounting type | screw fixing |
Side-by-side mounting | Yes |
Height | 214 mm |
Width | 160 mm |
Depth | 225 mm |
Required spacing | |
with side-by-side mounting | |
— forwards | 20 mm |
— upwards | 10 mm |
— downwards | 10 mm |
— at the side | 0 mm |
for grounded parts | |
— forwards | 20 mm |
— upwards | 10 mm |
— at the side | 10 mm |
— downwards | 10 mm |
for live parts | |
— forwards | 20 mm |
— upwards | 10 mm |
— downwards | 10 mm |
— at the side | 10 mm |
Connections/Terminals |
Type of electrical connection | |
for main current circuit | Connection bar |
for auxiliary and control current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
at AWG conductors for main contacts | 2/0 ... 500 kcmil |
Connectable conductor cross-section for main contacts | |
stranded | 70 ... 240 mm² |
Connectable conductor cross-section for auxiliary contacts | |
single or multi-stranded | 0.5 ... 4 mm² |
finely stranded with core end processing | 0.5 ... 2.5 mm² |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
— single or multi-stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) |
— finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
AWG number as coded connectable conductor cross section | |
for auxiliary contacts | 18 ... 14 |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 1 000 000 |
Product function | |
Mirror contact acc. to IEC 60947-4-1 | Yes |
positively driven operation acc. to IEC 60947-5-1 | No |
Protection against electrical shock | finger-safe when touched vertically from front acc. to IEC 60529 |