| Power contactor, AC-3 32 A, 15 kW / 400 V 24 V DC, 3-pole, Size S2, Screw terminal Reusable packaging Pack = 24 units !!! Phased-out product !!! Successor is SIRIUS 3RT2 Preferred successor type is |
Product brand name | SIRIUS |
Product designation | power contactor |
General technical data |
Size of contactor | S2 |
Insulation voltage | |
rated value | 690 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 6 kV |
maximum permissible voltage for safe isolation | |
between coil and main contacts acc. to EN 60947-1 | 400 V |
Protection class IP | |
on the front | IP20 |
of the terminal | IP00 |
Shock resistance at rectangular impulse | |
at DC | 10g / 5 ms, 5g / 10 ms |
Shock resistance with sine pulse | |
at DC | 15g / 5 ms, 8g / 10 ms |
Mechanical service life (switching cycles) | |
of contactor typical | 10 000 000 |
of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
of the contactor with added auxiliary switch block typical | 10 000 000 |
Reference code acc. to DIN EN 81346-2 | Q |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Main circuit |
Number of poles for main current circuit | 3 |
Number of NO contacts for main contacts | 3 |
Number of NC contacts for main contacts | 0 |
Operating current | |
at AC-1 at 400 V | |
— at ambient temperature 40 °C rated value | 50 A |
at AC-1 | |
— up to 690 V at ambient temperature 40 °C rated value | 50 A |
— up to 690 V at ambient temperature 60 °C rated value | 45 A |
at AC-3 | |
— at 400 V rated value | 32 A |
— at 690 V rated value | 20 A |
at AC-4 at 400 V rated value | 29 A |
Connectable conductor cross-section in main circuit at AC-1 | |
at 60 °C minimum permissible | 10 mm² |
at 40 °C minimum permissible | 16 mm² |
Operating current for approx. 200000 operating cycles at AC-4 | |
at 400 V rated value | 15.6 A |
at 690 V rated value | 11 A |
Operating current | |
at 1 current path at DC-1 | |
— at 24 V rated value | 45 A |
— at 110 V rated value | 4.5 A |
with 2 current paths in series at DC-1 | |
— at 24 V rated value | 45 A |
— at 110 V rated value | 25 A |
with 3 current paths in series at DC-1 | |
— at 24 V rated value | 45 A |
— at 110 V rated value | 45 A |
Operating current | |
at 1 current path at DC-3 at DC-5 | |
— at 24 V rated value | 35 A |
— at 110 V rated value | 2.5 A |
with 2 current paths in series at DC-3 at DC-5 | |
— at 24 V rated value | 45 A |
— at 110 V rated value | 25 A |
with 3 current paths in series at DC-3 at DC-5 | |
— at 24 V rated value | 45 A |
— at 110 V rated value | 45 A |
Operating power | |
at AC-1 | |
— at 230 V at 60 °C rated value | 18 kW |
— at 400 V rated value | 31 kW |
— at 690 V rated value | 54 kW |
— at 690 V at 60 °C rated value | 54 kW |
at AC-2 at 400 V rated value | 15 kW |
at AC-3 | |
— at 230 V rated value | 7.5 kW |
— at 400 V rated value | 15 kW |
— at 500 V rated value | 18.5 kW |
— at 690 V rated value | 18.5 kW |
Operating power for approx. 200000 operating cycles at AC-4 | |
at 400 V rated value | 8.2 kW |
at 690 V rated value | 10 kW |
Thermal short-time current limited to 10 s | 320 A |
Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor | 1.8 W |
No-load switching frequency | |
at DC | 1 500 1/h |
Operating frequency | |
at AC-1 maximum | 1 200 1/h |
at AC-2 maximum | 750 1/h |
at AC-3 maximum | 1 000 1/h |
at AC-4 maximum | 250 1/h |
Control circuit/ Control |
Type of voltage of the control supply voltage | DC |
Control supply voltage at DC | |
rated value | 24 V |
Operating range factor control supply voltage rated value of magnet coil at DC | |
initial value | 0.8 |
Full-scale value | 1.1 |
Closing power of magnet coil at DC | 13.3 W |
Holding power of magnet coil at DC | 13.3 W |
Closing delay | |
at DC | 50 ... 95 ms |
Opening delay | |
at DC | 20 ... 30 ms |
Arcing time | 10 ... 15 ms |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | |
instantaneous contact | 0 |
Number of NO contacts for auxiliary contacts | |
instantaneous contact | 0 |
Operating current at AC-12 maximum | 10 A |
Operating current at AC-15 | |
at 230 V rated value | 6 A |
at 400 V rated value | 3 A |
Operating current at DC-12 | |
at 60 V rated value | 6 A |
at 110 V rated value | 3 A |
at 220 V rated value | 1 A |
Operating current at DC-13 | |
at 24 V rated value | 10 A |
at 60 V rated value | 2 A |
at 110 V rated value | 1 A |
at 220 V rated value | 0.3 A |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
UL/CSA ratings |
Contact rating of auxiliary contacts according to UL | A600 / Q600 |
Short-circuit protection |
Design of the fuse link | |
for short-circuit protection of the main circuit | |
— with type of coordination 1 required | fuse gL/gG: 125 A |
— with type of assignment 2 required | fuse gL/gG: 63 A |
for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
Installation/ mounting/ dimensions |
| |
(mounting type) | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
Mounting type Side-by-side mounting | Yes |
Height | 112 mm |
Width | 55 mm |
Depth | 130 mm |
Required spacing | |
for grounded parts | |
— at the side | 6 mm |
Connections/Terminals |
Type of electrical connection | |
for main current circuit | screw-type terminals |
for auxiliary and control current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
for main contacts | |
— solid | 2x (0.75 ... 16 mm²) |
— stranded | 2x (0.75 ... 25 mm²) |
— single or multi-stranded | 2x (0,75 ... 16 mm²) |
— finely stranded with core end processing | 2x (0.75 ... 16 mm²) |
— finely stranded without core end processing | 2x (0.75 ... 16 mm²) |
at AWG conductors for main contacts | 2x (18 ... 2) |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
— finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |