3RR2241-2FW30
CURRENT MON. S00 STD. 24-240V UC SPRING

From SIEMENS

Monitoring relay, can be mounted to Contactor 3RT2, Size S00 standard, digitally adjustable Apparant/active current monitoring 1.6-16 A, 20-400 Hz, 3-phase Supply 24-240 V AC/DC 1 change-over contact, 1 semiconductor output for alarm and warning Monitoring for Current overshoot and undershoot Phase failure, Cable break Phase sequence Residual current Blocking current Warning and alarm thresholds with or without fault buffer ON delay 0-99 s Noise pulse suppression 0-30 s Pause after fault 0-300 min spring-type connection system
Product brand nameSIRIUS
Product designationMonitoring relays
Design of the productdigitally adjustable, 3-phase current monitoring
Product type designation3RR2
General technical data
Size of contactor can be combined company-specificS00
Operating apparent output rated value4 V·A
Insulation voltage
for overvoltage category III according to IEC 60664
— with degree of pollution 3 rated value690 V
Surge voltage resistance rated value6 kV
Protection class IP
on the frontIP20
of the terminalIP20
Shock resistance15g / 11 ms
Mechanical service life (switching cycles)
typical10 000 000
Electrical endurance (switching cycles)
at AC-15 at 230 V typical100 000
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference code acc. to DIN EN 81346-2K
Reference code acc. to DIN EN 61346-2K
Relative repeat accuracy2 %
Supply voltage
Type of voltage of the supply voltageAC/DC
Supply voltage 1 at AC
at 50 Hz24 ... 240 V
at 60 Hz24 ... 240 V
Supply voltage 1 at DC24 ... 240 V
Supply voltage frequency
150 ... 60 Hz
Measuring circuit
Type of current for monitoringAC
Adjustable pick-up value current
11.6 ... 16 A
21.6 ... 16 A
Adjustable response delay time
when starting0 ... 99 s
with lower or upper limit violation0 ... 30 s
Adjustable switching hysteresis for measured current value0.1 ... 3 A
Accuracy of digital display+/-1 digit
Precision
Temperature drift per °C0.1 %/°C
Communication/ Protocol
Protocol is supported
IO-Link protocolNo
Type of voltage supply via input/output link masterNo
Auxiliary circuit
Number of CO contacts
for auxiliary contacts1
Operating current of auxiliary contacts at AC-15
at 24 V3 A
at 230 V3 A
at 400 V3 A
Operating current of auxiliary contacts at DC-13
at 24 V1 A
at 125 V0.2 A
at 250 V0.1 A
Contact rating of auxiliary contacts according to ULB300 / R300
Main circuit
Operating power
rated value2.5 W
Outputs
Operating current at 17 V minimum5 mA
Electromagnetic compatibility
EMC emitted interference
acc. to IEC 60947-1ambience A (industrial sector)
EMI immunity
acc. to IEC 60947-1ambience A (industrial sector)
Safety related data
Protection against electrical shockfinger-safe
Connections/Terminals
Product function
removable terminal for main circuitNo
removable terminal for auxiliary and control circuitYes
Type of electrical connection
for main current circuitspring-loaded terminals
for auxiliary and control current circuitspring-loaded terminals
Type of connectable conductor cross-sections
for main contacts
— solid1x (0.5 ... 4 mm²)
— finely stranded with core end processing1x (0.5 ... 2.5 mm²)
— finely stranded without core end processing1x (0.5 ... 2.5 mm²)
at AWG conductors for main contacts1x (20 ... 12)
Connectable conductor cross-section for main contacts
single or multi-stranded0.5 ... 4 mm²
finely stranded with core end processing2.5 ... 2.5 mm²
finely stranded without core end processing0.5 ... 2.5 mm²
Type of connectable conductor cross-sections
for auxiliary contacts
— solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing2x (0.25 ... 1.5 mm²)
— finely stranded without core end processing2x (0.25 ... 1.5 mm²)
at AWG conductors for auxiliary contacts2x (24 ... 16)
AWG number as coded connectable conductor cross section
for main contacts20 ... 12
Tightening torque
with screw-type terminals0.8 ... 1.2 N·m
Installation/ mounting/ dimensions
Mounting positionany
Mounting typedirect mounting
Height90 mm
Width45 mm
Depth80 mm
Required spacing
with side-by-side mounting
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
for grounded parts
— forwards6 mm
— Backwards0 mm
— upwards0 mm
— at the side6 mm
— downwards0 mm
for live parts
— forwards6 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side6 mm
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-25 ... +60 °C
during storage-40 ... +80 °C

External links