3RP1505-1BP30-ZX95
TIME RELAY, MULTI-FUNCTION

From SIEMENS

Timing relay, Multifunction Phased-out product !!! For further information, please contact our sales department 2 change-over contacts, 16 functions 15 time ranges (0.05 s-100 h) 24 V 200 ... 240 V AC and 24 V DC at 50/60 Hz AC with LED, screw terminal Pack = 137 units
Product brand nameSIRIUS
Product designationtiming relay
Product type designation3RP15
General technical data
Product component
Relay outputYes
semi-conductor outputNo
Product extension required remote controlNo
Product extension optional remote controlNo
Power loss [W] total typical2 W
Insulation voltage
for overvoltage category III according to IEC 60664
— with degree of pollution 3 rated value300 V
Test voltage for isolation test2 kV
Degree of pollution3
Surge voltage resistance rated value4 000 V
Protection class IPIP20
Shock resistance
acc. to IEC 60068-2-2711g / 15 ms
Mechanical service life (switching cycles)
typical10 000 000
Electrical endurance (switching cycles)
at AC-15 at 230 V typical100 000
Adjustable time0.05 s ... 100 h
Relative setting accuracy relating to full-scale value5 %
Thermal current5 A
Minimum ON period35 ms
Recovery time150 ms
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference code acc. to DIN EN 81346-2K
Reference code acc. to DIN EN 61346-2K
Relative repeat accuracy1 %
Control circuit/ Control
Type of voltage of the control supply voltageAC/DC
Control supply voltage 1 at AC
at 50 Hz rated value24 V
at 60 Hz rated value24 V
Control supply voltage 2 at AC
at 50 Hz200 ... 240 V
at 60 Hz200 ... 240 V
Control supply voltage frequency 150 ... 60 Hz
Control supply voltage 1
at DC rated value24 V
Operating range factor control supply voltage rated value at DC
initial value0.85
Full-scale value1.1
Operating range factor control supply voltage rated value at AC at 50 Hz
initial value0.85
Full-scale value1.1
Operating range factor control supply voltage rated value at AC at 60 Hz
initial value0.85
Full-scale value1.1
Switching Function
Switching function
ON-delayYes
ON-delay/instantaneous contactYes
passing make contactYes
passing make contact/instantaneous contactYes
OFF delayNo
Switching function
flashing symmetrically starting with interval/instantaneousYes
flashing symmetrically starting with intervalYes
flashing symmetrically starting with pulse/instantaneousNo
flashing symmetrically starting with pulseNo
flashing asymmetrically starting with intervalNo
flashing asymmetrically starting with pulseNo
Switching function
star-delta circuit with delay timeNo
star-delta circuitYes
Switching function with control signal
additive ON delayYes
passing break contactYes
passing break contact/instantaneousYes
OFF delayYes
OFF delay/instantaneousYes
pulse delayedNo
pulse delayed/instantaneousNo
pulse-shapingYes
pulse-shaping/instantaneousYes
additive ON delay/instantaneousYes
ON-delay/OFF-delay/instantaneousYes
passing make contactNo
passing make contact/instantaneous contactNo
Switching function of interval relay with control signal
retrotriggerable with deactivated control signal/instantaneous contactNo
retrotriggerable with activated control signalNo
retrotriggerable with activated control signal/instantaneous contactNo
retriggerable with deactivated control signalNo
Design of the control terminal non-floatingYes
Short-circuit protection
Design of the fuse link
for short-circuit protection of the auxiliary switch requiredfuse gL/gG: 4 A
Auxiliary circuit
Material of switching contactsAgSnO2
Number of CO contacts
delayed switching2
Operating current of auxiliary contacts at AC-15
at 24 V3 A
at 250 V3 A
Operating current of auxiliary contacts at DC-13
at 24 V1 A
at 125 V0.2 A
at 250 V0.1 A
Operating frequency with 3RT2 contactor maximum5 000 1/h
Contact reliability of auxiliary contactsone incorrect switching operation of 100 million switching operations (17 V, 5 mA)
Contact rating of auxiliary contacts according to ULR300 / B300
Influence of the surrounding temperature±5 %
Power supply influence±1 %
Inputs/ Outputs
Product function
non-volatileNo
Electromagnetic compatibility
EMI immunity
acc. to IEC 61812-1EN 61000-6-2
Conducted interference
due to burst acc. to IEC 61000-4-42 kV network connection / 1 kV control connection
due to conductor-earth surge acc. to IEC 61000-4-52 kV
due to conductor-conductor surge acc. to IEC 61000-4-51 kV
Field-bound parasitic coupling acc. to IEC 61000-4-310 V/m
Electrostatic discharge acc. to IEC 61000-4-24 kV contact discharge / 8 kV air discharge
Safety related data
Protection against electrical shockfinger-safe
Type of insulationBasic insulation
Category acc. to EN 954-1none
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitYes
Type of electrical connection
for auxiliary and control current circuitscrew-type terminals
Type of connectable conductor cross-sections
solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
at AWG conductors solid2x (20 ... 14)
at AWG conductors stranded2x (20 ... 14)
Connectable conductor cross-section
solid0.5 ... 4 mm²
finely stranded with core end processing0.5 ... 2.5 mm²
AWG number as coded connectable conductor cross section
solid20 ... 14
stranded20 ... 14
Tightening torque0.8 ... 1.2 N·m
Design of the thread of the connection screwM3
Installation/ mounting/ dimensions
Mounting positionany
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail
Height102 mm
Width22.5 mm
Depth91 mm
Required spacing
with side-by-side mounting
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
for grounded parts
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— at the side0 mm
— downwards0 mm
for live parts
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-25 ... +60 °C
during storage-40 ... +85 °C
during transport-40 ... +85 °C
Relative humidity
during operation10 ... 95 %

External links