3RK1901-1MX01 AS-INTERFACE ACCESSORIES
From SIEMENS
AS-i Extension Plug Plus Phased-out product !!! For further information, please contact our sales department Doubling of the cable length to 200 m pro AS-i Segment with integrated slave for diagnostics Degree of protection IP67 Connection via AS-Interface M12 branch 3RX9801-0AA00 must be ordered separately | |||
General technical data: | |||
Design of the product | AS-Interface Extension Plug Plus | ||
Design of the slave type | A/B slave | ||
Voltage supply using AS-Interface | Yes | ||
I/O configuration | B | ||
ID/ID2 code | I/O | ||
Operating voltage acc. to AS Interface specification | V | 26.5 ... 31.6 | |
Assignment of data bits | |||
D0 | OUT1 | ||
D1 | OUT2 | ||
D2 | IN3 | ||
D3 | IN4 | ||
Function | |||
Out1 | not required | ||
Out2 | switching threshold parameterization: D1 = 0: Switching threshold 26. 5 V D1 = 1 : Switching threshold 23 V | ||
IN3 | undervoltage evaluation: D2 = 0: Undervoltage > 50 ms D2 = 1: No undervoltage | ||
IN4 | undervoltage evaluation: D3 = 0: Undervoltage > 5 ms D3 = 1: No undervoltage | ||
Status display | |||
U AS-Interface | none | ||
Connections/ Terminals: | |||
Design of the AS-Interface connection | Connection via AS-Interface M12 feeder 3RX9801-0AA00 | ||
AS interface | |||
Connection Polarity reversal protection | yes | ||
total current input max | mA | 15 | |
AS-Interface bus connection pin assignment | |||
PIN1 | U AS-Interface + | ||
PIN3 | U AS-Interface - | ||
Ambient conditions: | |||
Ambient temperature during operation | °C | -25 ... +85 | |
Protection class IP | IP67 |