3RK1300-0DS01-1AA3
EM 300 RS, FOR ET 200 X,

From SIEMENS

Field Device Coupler FDC 157 physical interface for PROFIBUS PA or Foundation Fieldbus H1 integrated bus supply up to 1000 mA with redundancy capability integrated diagnostics Degree of protection IP20 for extended temperature range
General information
Product type designationField Device Connection FDC157
Product descriptionField Device Coupler for PROFIBUS PA and Foundation Fieldbus
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Overvoltage protectionYes
Mains buffering
Mains/voltage failure stored energy time5 ms
Input current
Current consumption, max.2.3 A; at 24 V DC
Power loss
Power loss, typ.13.4 W
Interfaces
PROFIBUS DP
Transmission rate, max.45.45 kbit/s
Design of electrical connection of PROFIBUS interface9-pin sub D
PROFIBUS PA
Transmission rate, max.31.25 kbit/s
Number of connectable PA field devices31
Current output to PA field devices, max.1 A
Protocols
PROFIBUS DPYes
PROFIBUS PAYes
Interrupts/diagnostics/status information
Status indicatorYes; Group error (red)
AlarmsYes
Diagnostics functionYes
Diagnostics indication LED
Bus activity DP (yellow)Yes
Bus activity PA (yellow)Yes
Bus fault BF (red)Yes
Group error SF (red)Yes
Monitoring 24 V voltage supply ON (green)Yes
Potential separation
between backplane bus and all other circuit componentsYes
between PROFIBUS DP and all other circuit componentsYes
between PROFIBUS PA and all other circuit componentsYes
between supply and all other circuitsYes
Isolation
Isolation tested with600 V DC
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Ambient conditions
Ambient temperature during operation
min.-25 °C
max.60 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Relative humidity
Operation, max.95 %
Dimensions
Width80 mm
Height125 mm
Depth130 mm
Weights
Weight, approx.550 g
last modified:03/04/2019

External links