| Attachable block, 4-pole, 4 NO EN 50005 ! Phased-out product! Successor is SIRIUS 3RH2 |
General technical data |
Product brand name | SIRIUS |
Suitability for use | Contactor relay and power contactor |
Protection class IP on the front | IP20 |
Ambient temperature | |
during storage | -55 ... +80 °C |
during operation | -25 ... +60 °C |
Mechanical service life (switching cycles) typical | 10 000 000 |
Electrical endurance (switching cycles) at AC-15 at 230 V typical | 200 000 |
Contact reliability | one incorrect switching operation of 100 million switching operations (17 V, 5 mA) |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
Insulation voltage with degree of pollution 3 rated value | 690 V |
Surge voltage resistance rated value | 6 kV |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | |
instantaneous contact | 0 |
Number of NO contacts for auxiliary contacts | |
instantaneous contact | 4 |
Operating current of auxiliary contacts at AC-12 | |
at 24 V | 10 A |
at 230 V | 10 A |
maximum | 10 A |
Operating current | |
of auxiliary contacts | |
— at AC-14 | |
— at 125 V | 6 A |
— at 250 V | 6 A |
— at AC-15 | |
— at 24 V | 6 A |
— at 230 V | 6 A |
— at 400 V | 3 A |
at AC-15 at 690 V rated value | 1 A |
Operating current | |
of auxiliary contacts at DC-12 | |
— at 24 V | 10 A |
— at 110 V | 3 A |
— at 220 V | 1 A |
with 2 current paths in series at DC-12 | |
— at 24 V rated value | 10 A |
— at 60 V rated value | 10 A |
— at 110 V rated value | 4 A |
— at 220 V rated value | 2 A |
— at 440 V rated value | 1.3 A |
— at 600 V rated value | 0.65 A |
with 3 current paths in series at DC-12 | |
— at 24 V rated value | 10 A |
— at 60 V rated value | 10 A |
— at 110 V rated value | 10 A |
— at 220 V rated value | 3.6 A |
— at 440 V rated value | 2.5 A |
— at 600 V rated value | 1.8 A |
Operating current | |
of auxiliary contacts at DC-13 | |
— at 24 V | 6 A |
— at 60 V | 2 A |
— at 110 V | 1 A |
— at 220 V | 0.3 A |
with 2 current paths in series at DC-13 | |
— at 24 V rated value | 10 A |
— at 60 V rated value | 3.5 A |
— at 110 V rated value | 1.3 A |
— at 220 V rated value | 0.9 A |
— at 440 V rated value | 0.2 A |
— at 600 V rated value | 0.1 A |
with 3 current paths in series at DC-13 | |
— at 24 V rated value | 10 A |
— at 60 V rated value | 4.7 A |
— at 110 V rated value | 3 A |
— at 220 V rated value | 1.2 A |
— at 440 V rated value | 0.5 A |
— at 600 V rated value | 0.26 A |
Installation/ mounting/ dimensions |
Mounting type | snap-on mounting |
Width | 44 mm |
Height | 38 mm |
Depth | 51 mm |
Connections/Terminals |
Type of electrical connection for auxiliary and control current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— finely stranded | |
— with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
Safety related data |
Product function Mirror contact acc. to IEC 60947-4-1 | Yes |
Note | with 3RT1 |
Product function positively driven operation acc. to IEC 60947-5-1 | No |