| Contactor relay, 3 NO + 1 NC 24 V DC Spring-type terminal Size S00 !!! Phased-out product !!! Successor is SIRIUS 3RH2 |
Product brand name | SIRIUS |
Product designation | Auxiliary contactor |
General technical data |
Size of contactor | S00 |
Product extension | |
Auxiliary switch | Yes |
Insulation voltage | |
with degree of pollution 3 rated value | 690 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 6 kV |
Protection class IP | |
on the front | IP20 |
Shock resistance | 10g / 5 ms and 5g / 10 ms |
Mechanical service life (switching cycles) | |
of contactor typical | 30 000 000 |
of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
of the contactor with added auxiliary switch block typical | 10 000 000 |
Reference code acc. to DIN EN 81346-2 | K |
Reference code acc. to DIN EN 61346-2 | K |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Control circuit/ Control |
Type of voltage of the control supply voltage | DC |
Control supply voltage at DC | |
rated value | 24 V |
Operating range factor control supply voltage rated value of magnet coil at DC | |
initial value | 0.8 |
Full-scale value | 1.1 |
Closing power of magnet coil at DC | 3.2 W |
Holding power of magnet coil at DC | 3.2 W |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | 1 |
instantaneous contact | 1 |
delayed switching | 0 |
lagging switching | 0 |
make-before-break switching | 0 |
Number of NO contacts for auxiliary contacts | 3 |
instantaneous contact | 3 |
delayed switching | 0 |
leading contact | 0 |
make-before-break switching | 0 |
Number of CO contacts | |
for auxiliary contacts | 0 |
of auxiliary contacts instantaneous contact | 0 |
Identification number and letter for switching elements | 31 E |
Operating current at AC-12 maximum | 10 A |
Operating current at AC-15 | |
at 230 V rated value | 6 A |
at 400 V rated value | 3 A |
at 500 V rated value | 2 A |
at 690 V rated value | 1 A |
Operating current at 1 current path at DC-12 | |
at 24 V rated value | 10 A |
at 110 V rated value | 3 A |
at 220 V rated value | 1 A |
Operating current at 1 current path at DC-13 | |
at 24 V rated value | 10 A |
at 110 V rated value | 1 A |
at 220 V rated value | 0.27 A |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
Short-circuit protection |
Design of the fuse link | |
for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
Installation/ mounting/ dimensions |
Mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| |
(mounting type) | screw and snap-on mounting |
Height | 60 mm |
Width | 45 mm |
Depth | 73 mm |
Required spacing | |
with side-by-side mounting | |
— at the side | 0 mm |
Connections/Terminals |
Type of electrical connection | |
for auxiliary and control current circuit | Cage Clamp terminals |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— solid | 2x (0.25 ... 2.5 mm²) |
— finely stranded with core end processing | 2x (0.25 ... 1.5 mm²) |
— finely stranded without core end processing | 2x (0.25 ... 2.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (24 ... 14) |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 1 000 000; With 0.3 x Ie |
Proportion of dangerous failures | |
with low demand rate acc. to SN 31920 | 40 % |
with high demand rate acc. to SN 31920 | 75 % |
T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |