| Contactor relay, 2 NO + 1 NC 125 V DC 0.7...1.25* Us With varistor Railway version Optimum installation on standard mounting rail 20 G !!! Phased-out product !!! Successor is SIRIUS 3RH2 Preferred successor type is >>3RH2122-1KG40-0LA4<< |
Product brand name | SIRIUS |
Product designation | Auxiliary contactor |
General technical data |
Size of contactor | S00 |
Product extension | |
Auxiliary switch | Yes |
Insulation voltage | |
with degree of pollution 3 rated value | 690 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 6 kV |
Protection class IP | |
on the front | IP20 |
Shock resistance | 10g / 5 ms and 5g / 10 ms |
Mechanical service life (switching cycles) | |
of contactor typical | 30 000 000 |
of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
of the contactor with added auxiliary switch block typical | 10 000 000 |
Reference code acc. to DIN EN 81346-2 | K |
Reference code acc. to DIN EN 61346-2 | K |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -40 ... +70 °C |
during storage | -55 ... +80 °C |
during transport | -55 ... +80 °C |
Control circuit/ Control |
Type of voltage of the control supply voltage | DC |
Control supply voltage at DC | |
rated value | 125 V |
Operating range factor control supply voltage rated value of magnet coil at DC | |
initial value | 0.7 |
Full-scale value | 1.25 |
Design of the surge suppressor | with varistor |
Closing power of magnet coil at DC | 11 W |
Holding power of magnet coil at DC | 4 W |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | 1 |
instantaneous contact | 1 |
delayed switching | 0 |
lagging switching | 0 |
make-before-break switching | 0 |
Number of NO contacts for auxiliary contacts | 2 |
instantaneous contact | 2 |
delayed switching | 0 |
leading contact | 0 |
make-before-break switching | 0 |
Number of CO contacts | |
for auxiliary contacts | 0 |
of auxiliary contacts instantaneous contact | 0 |
Identification number and letter for switching elements | 21 E |
Operating current at AC-12 maximum | 10 A |
Operating current at AC-15 | |
at 230 V rated value | 6 A |
at 400 V rated value | 3 A |
at 500 V rated value | 2 A |
at 690 V rated value | 1 A |
Operating current at 1 current path at DC-12 | |
at 24 V rated value | 10 A |
at 110 V rated value | 3 A |
at 220 V rated value | 1 A |
Operating current at 1 current path at DC-13 | |
at 24 V rated value | 10 A |
at 110 V rated value | 1 A |
at 220 V rated value | 0.27 A |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
Short-circuit protection |
Design of the fuse link | |
for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
Installation/ mounting/ dimensions |
Mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
Mounting type | screw and snap-on mounting |
Height | 57.5 mm |
Width | 45 mm |
Depth | 72 mm |
Required spacing | |
with side-by-side mounting | |
— at the side | 0 mm |
Connections/Terminals |
Type of electrical connection | |
for auxiliary and control current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
— finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 1 000 000; With 0.3 x Ie |
Proportion of dangerous failures | |
with low demand rate acc. to SN 31920 | 70 % |
with high demand rate acc. to SN 31920 | 75 % |
T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |