3RG9001-0AA00 ACTUATOR SENSOR INTERFACE
From SIEMENS
AS Interface user module IP67 Phased-out product !!! For further information, please contact our sales department digital, 4 DI 4 x 1 input, max. 100 mA, PNP 4 x M12 socket | |||
General technical data: | |||
Design of the product | digital I/O modules for operation in the field, IP67 - user modules | ||
Design of the slave type | standard slave | ||
Type | 4 inputs | ||
I/O configuration | 0 | ||
ID code | 0 | ||
Number I/O sockets | 4 | ||
Protocol is supported AS-interface protocol | Yes | ||
Type of electrical connection of the inputs and outputs | M12 screw-type terminals | ||
AS interface total current input max | mA | 120 | |
operating voltage according to AS-Interface spezification | V | 26.5 ... 31.6 | |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | A | ||
Reference code acc. to DIN EN 61346-2 | K | ||
Inputs: | |||
Number of digital inputs | 4 | ||
Input circuit | PNP | ||
Type of voltage of the input voltages | DC | ||
Input voltage | V | 20 ... 30 | |
Inputs switching level High min | V | 10 | |
Input current at digital input | |||
for signal <1> minimum | mA | 5 | |
with signal <0> maximum | mA | 1.5 | |
Inputs sensor supply using AS-Interface | short-circuit and overload resistant | ||
Design of the pin assignment of the inputs | standard assignement | ||
Outputs: | |||
Number of digital outputs | 0 | ||
Design of the pin assignment of the outputs | standard assignement | ||
Property of the output Short-circuit proof | No | ||
Status display | |||
display of I/Os | yellow LED | ||
display of AS-Interface/diagnostics | green LED | ||
Assignment of data bits | |||
socket | input (D0) | ||
socket 2 | input (D1) | ||
socket 3 | input (D2) | ||
socket 4 | input (D3) | ||
Ambient conditions: | |||
Ambient temperature | |||
during storage | °C | -40 ... +85 | |
during operation | °C | -25 ... +85 | |
Protection class IP | IP67 | ||
Mechanical data: | |||
Width | mm | 45 | |
Height | mm | 80 | |
Depth | mm | 27 | |
Mounting type | standard rail mounting/wall mounting using coupling module | ||
connection | using contact pins on FK or Pg coupling module | ||
Type of connection | 2- and 3-wire technology |