3RF2990-0GA36
LOAD MONITORING

From SIEMENS

Load monitoring Current range 90 A / 40 °C 400-600 V / 110 V AC for semiconductor relay / contactor
General technical data
Product brand nameSIRIUS
Product designationload monitoring
Product functionsolid-state relay / solid-state contactor 3RF2
Number of poles for main current circuit0
Protection class IPIP20
Product designation _1 of the accessories that can be orderedsealable end cover
Manufacturer's article number _1 of the accessories that can be ordered
Hole diameter of the current transformermm17
Number of partial loads for load monitoring12
Ambient temperature
during operation°C-25 ... +60
during storage°C-55 ... +80
Installation altitude at height above sea level maximumm1 000
Vibration resistance acc. to IEC 60068-2-62g
Shock resistance acc. to IEC 60068-2-2715g / 11 ms
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750A
Reference code acc. to DIN EN 61346-2B
Main circuit
Number of NO contacts for main contacts0
Number of NC contacts for main contacts0
Operating current
at AC-1 at 400 V rated valueA90
Derating temperature°C40
Operating voltage at AC
at 50 Hz rated valueV400 ... 600
at 60 Hz rated valueV400 ... 600
Operating range relative to the operating voltage at AC
at 50 HzV340 ... 660
at 60 HzV340 ... 660
Operating frequency rated valueHz50 ... 60
Relative symmetrical tolerance of the operating frequency%10
Insulation voltage rated valueV600
Compensation of the supply voltage fluctuations%20
Partial load for load monitoringA2.9
Teach range currentA2.93 ... 90
Current measuring rangeA0 ... 99
Control circuit/ Control
Type of voltageAC
Control supply voltage
at AC
— at 50 Hz
— rated valueV90 ... 121
— Full-scale value for signal<0> recognitionV15
— at 60 Hz
— rated valueV90 ... 121
— Full-scale value for signal<0> recognitionV15
Supply voltage frequency for auxiliary and control current circuit rated valueHz50 ... 60
Symmetrical line frequency toleranceHz5
Relative symmetrical tolerance of the supply voltage frequency%10
Control current
at AC rated valuemA20
Response delays0.1 ... 3
Auxiliary circuit
Number of NC contacts for auxiliary contacts1
Number of NO contacts for auxiliary contacts1
Number of CO contacts for auxiliary contacts1
Operating voltage of auxiliary contacts
at ACV90 ... 121
at DCV90 ... 121
Operating current of auxiliary contacts
at ACmA5 ... 1 000
at DCmA5 ... 1 000
Installation/ mounting/ dimensions
Mounting typeclip-on
Mounting type Side-by-side mountingYes
Widthmm45
Heightmm111.5
Depthmm69.5
Connections/Terminals
Type of electrical connection
for auxiliary and control current circuitscrew-type terminals
Design of the thread of the connection screw of the auxiliary and control contactsM3
Type of connectable conductor cross-sections
for auxiliary and control contacts
— solid1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— finely stranded
— with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— without core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
at AWG conductors for auxiliary and control contacts1x (AWG 20 ... 12)
Connectable conductor cross-section for auxiliary and control contacts
solidmm²0.5 ... 2.5
finely stranded
— with core end processingmm²0.5 ... 2.5
— without core end processingmm²0.5 ... 2.5
AWG number as coded connectable conductor cross section for auxiliary and control contacts12 ... 20
Wire stripping length of the cable for auxiliary and control contactsmm7
Tightening torque for auxiliary and control contacts with screw-type terminalsN·m0.5 ... 0.6
Tightening torque [lbf·in] for auxiliary and control contacts with screw-type terminalslbf·in4.5 ... 5.3