| Solid-state contactor 1-phase 3RF2 AC 51 / 50 A / 40 °C 48-600 V / 4-30 V DC screw terminal Blocking voltage 1200 V |
General technical data |
Product brand name | | SIRIUS |
Product designation | | solid-state contactor |
Product function | | zero-point switching |
Number of poles for main current circuit | | 1 |
Protection class IP | | IP20 |
Product designation _1 of the accessories that can be ordered | | terminal cover |
Manufacturer's article number _1 of the accessories that can be ordered | | |
Product designation _3 of the accessories that can be ordered | | converter |
Manufacturer's article number _3 of the accessories that can be ordered | | |
Product designation _4 of the accessories that can be ordered | | load monitoring |
Manufacturer's article number _4 of the accessories that can be ordered | | |
Ambient temperature | | |
during operation | °C | -25 ... +60 |
during storage | °C | -55 ... +80 |
Installation altitude at height above sea level maximum | m | 1 000 |
Vibration resistance acc. to IEC 60068-2-6 | | 2g |
Shock resistance acc. to IEC 60068-2-27 | | 15g / 11 ms |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | | K |
Reference code acc. to DIN EN 61346-2 | | Q |
Number of NC contacts for auxiliary contacts | | 0 |
Number of NO contacts for auxiliary contacts | | 0 |
Number of CO contacts for auxiliary contacts | | 0 |
Main circuit |
Number of NO contacts for main contacts | | 1 |
Number of NC contacts for main contacts | | 0 |
Operating current | | |
minimum | mA | 500 |
at AC-51 rated value | A | 50 |
at AC-51 acc. to IEC 60947-4-3 | A | 36 |
Derating temperature | °C | 40 |
Power loss [W] total typical | W | 54 |
Reverse current of the thyristor | mA | 10 |
Blocking voltage at the thyristor for main contacts maximum permissible | V | 1 200 |
Rate of voltage rise at the thyristor for main contacts maximum permissible | V/µs | 1 000 |
Surge current resistance rated value | A | 1 150 |
I2t value maximum | A²·s | 6 600 |
Operating voltage at AC | | |
at 60 Hz rated value | V | 48 ... 600 |
at 50 Hz rated value | V | 48 ... 600 |
Operating range relative to the operating voltage at AC | | |
at 50 Hz | V | 40 ... 660 |
at 60 Hz | V | 40 ... 660 |
Operating frequency rated value | Hz | 50 ... 60 |
Insulation voltage rated value | V | 600 |
Control circuit/ Control |
Type of voltage of the control supply voltage | | DC |
Control supply voltage 1 | | |
at DC | | |
— Initial rated value | V | 4 |
— Final rated value | V | 30 |
— rated value maximum permissible | V | 30 |
Control supply voltage | | |
at DC initial value for signal <1> detection | V | 4 |
at DC Full-scale value for signal<0> recognition | V | 1 |
Control current | | |
at DC rated value | mA | 20 |
Installation/ mounting/ dimensions |
Mounting type | | screw and snap-on mounting onto 35 mm standard mounting rail |
Mounting type Side-by-side mounting | | Yes |
Design of the thread of the screw for securing the equipment | | M4 |
Tightening torque of the screw for securing the equipment | N·m | 1.5 |
Width | mm | 67.5 |
Height | mm | 100 |
Depth | mm | 142; 156.0 mm up to product revision E05 |
Connections/Terminals |
Type of electrical connection for main current circuit | | screw-type terminals |
Design of the thread of the connection screw for main contacts | | M4 |
Tightening torque for main contacts with screw-type terminals | N·m | 2 ... 2.5 |
Tightening torque [lbf·in] for main contacts with screw-type terminals | lbf·in | 18 ... 22 |
Type of connectable conductor cross-sections for main contacts | | |
solid | | 2x (1.5 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
finely stranded | | |
— with core end processing | | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm² |
Type of connectable conductor cross-sections | | |
at AWG conductors | | |
— for main contacts | | 2x (14 ... 10) |
— for auxiliary and control contacts | | 1x (AWG 20 ... 12) |
Type of connectable conductor cross-sections for auxiliary and control contacts | | |
solid | | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²) |
finely stranded | | |
— with core end processing | | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²) |
— without core end processing | | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²) |
Connectable conductor cross-section | | |
for main contacts | | |
— single or multi-stranded | mm² | 1.5 ... 6 |
— finely stranded | | |
— with core end processing | mm² | 1 ... 10 |
for auxiliary and control contacts | | |
— solid | mm² | 0.5 ... 2.5 |
— finely stranded | | |
— with core end processing | mm² | 0.5 ... 2.5 |
— without core end processing | mm² | 0.5 ... 2.5 |
AWG number as coded connectable conductor cross section | | |
for main contacts | | 10 ... 14 |
for auxiliary and control contacts | | 20 ... 12 |
Type of electrical connection for auxiliary and control current circuit | | screw-type terminals |
Design of the thread of the connection screw of the auxiliary and control contacts | | M3 |
Wire stripping length of the cable | | |
for main contacts | mm | 7 |
for auxiliary and control contacts | mm | 7 |
Tightening torque for auxiliary and control contacts with screw-type terminals | N·m | 0.5 ... 0.6 |
Tightening torque [lbf·in] for auxiliary and control contacts with screw-type terminals | lbf·in | 4.5 ... 5.3 |