3RF2330-1AA44
SEMICONDUCTOR CONTACTOR 3RF2

From SIEMENS

Solid-state contactor 1-phase 3RF2 AC 51 / 30 A / 40 °C 48-460 V / 4-30 V DC screw terminal
Product brand nameSIRIUS
Product designationsolid-state contactor
Product type designation3RF23
Manufacturer's article number
_1 / of the accessories that can be ordered
_3 / of the accessories that can be ordered
_4 / of the accessories that can be ordered
_5 / of the accessories that can be ordered
Product designation
_1 / of the accessories that can be orderedterminal cover
_3 / of the accessories that can be orderedconverter
_4 / of the accessories that can be orderedload monitoring
_5 / of the accessories that can be orderedload monitoring, basis
General technical data
Product functionzero-point switching
Power loss [W] / for rated value of the current / at AC / in hot operating state33 W
Insulation voltage
rated value600 V
Degree of pollution3
Protection class IPIP20
Shock resistance / acc. to IEC 60068-2-2715g / 11 ms
Vibration resistance / acc. to IEC 60068-2-62g
Reference code / acc. to DIN 40719 extended according to IEC 204-2 / acc. to IEC 750K
Reference code / acc. to DIN EN 81346-2Q
Reference code / acc. to DIN EN 61346-2Q
Main circuit
Number of poles / for main current circuit1
Number of NO contacts / for main contacts1
Number of NC contacts / for main contacts0
Operating voltage / at AC
at 50 Hz / rated value48 ... 460 V
at 60 Hz / rated value48 ... 460 V
Operating frequency / rated value50 ... 60 Hz
Operating range relative to the operating voltage / at AC
at 50 Hz40 ... 506 V
at 60 Hz40 ... 506 V
Operating current
at AC-51 / rated value30 A
Operating current / minimum500 mA
Rate of voltage rise / at the thyristor / for main contacts / maximum permissible1 000 V/µs
Blocking voltage / at the thyristor / for main contacts / maximum permissible1 200 V
Reverse current / of the thyristor10 mA
Derating temperature40 °C
Surge current resistance / rated value600 A
I2t value / maximum1 800 A²·s
Control circuit/ Control
Type of voltage / of the control supply voltageDC
Control supply voltage / 1
at DC / rated value30 V
at DC4 ... 30 V
Control supply voltage
at DC / initial value for signal <1> detection4 V
at DC / Full-scale value for signal<0> recognition1 V
Control current / at DC / rated value20 mA
Switch-on delay time1 ms; additionally max. one half-wave
Off-delay time1 ms; additionally max. one half-wave
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Number of CO contacts / for auxiliary contacts0
Installation/ mounting/ dimensions
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail
Side-by-side mountingYes
Height100 mm
Width45 mm
Depth139 mm; 157.0 mm up to product revision E05
Installation altitude / at height above sea level / maximum1 000 m
Connections/ Terminals
Type of connectable conductor cross-sections
for main contacts
— solid2x (1.5 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
— finely stranded / with core end processing2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
at AWG conductors / for main contacts2x (14 ... 10)
Type of connectable conductor cross-sections
for auxiliary and control contacts
— solid1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— finely stranded / with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— finely stranded / without core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
at AWG conductors / for auxiliary and control contacts1x (AWG 20 ... 12)
Tightening torque
for main contacts / with screw-type terminals2 ... 2.5 N·m
for auxiliary and control contacts / with screw-type terminals0.5 ... 0.6 N·m
Tightening torque [lbf·in]
for main contacts / with screw-type terminals18 ... 22 lbf·in
for auxiliary and control contacts / with screw-type terminals4.5 ... 5.3 lbf·in
Design of the thread / of the connection screw
for main contactsM4
of the auxiliary and control contactsM3
Wire stripping length / of the cable
for main contacts7 mm
for auxiliary and control contacts7 mm
Ambient conditions
Ambient temperature
during operation-25 ... +60 °C
during storage-55 ... +80 °C
Electromagnetic compatibility
Conducted interference
due to burst / acc. to IEC 61000-4-42 kV / 5 kHz behavior criterion 2
due to conductor-earth surge / acc. to IEC 61000-4-52 kV behavior criterion 2
due to conductor-conductor surge / acc. to IEC 61000-4-51 kV behavior criterion 2
due to high-frequency radiation / acc. to IEC 61000-4-6140 dBuV in the frequency range 0.15 ... 80 MHz, behavior criterion 1
Electrostatic discharge / acc. to IEC 61000-4-24 kV contact discharging / 8 kV air discharging, behavior criterion 2
Conducted HF-interference emissions / acc. to CISPR11Class A for industrial environment
Field-bound HF-interference emission / acc. to CISPR11Class B for the domestic, business and commercial environments