| In-line fuse switch disconnector 3-pole selectable, Sz. 3 I=630 A, U=690 V Screw terminal M12, new design Current transformer installation possible |
Model |
Product brand name | SENTRON |
Product designation | Fuse switch disconnectors |
Design of the product | in in-line design |
Design type | Fixed-mounted |
Type of switching contact / double breaking switching contact | No |
Design of the auxiliary release | No |
Design of the auxiliary switch | No |
Version of fuse monitoring | Without |
Design of the load switch / Strip form | Yes |
General technical data |
Number of poles | 3 |
Number of poles / Note | 3-pole switchable |
Type of device | For busbar system 185 mm |
Size of fuse link | NH2, NH3 |
Continuous current / at 35 °C / rated value | 630 A |
cut-off value I**2t,max. / 500 V | 5 400 000 A²·s |
circuit-breaker / Design | 3NJ4 |
Fuse system | LV HRC fuse |
Voltage |
Insulation voltage / rated value | 1 000 V |
Protection class |
Protection class IP / on the front | IP30 |
Dissipation |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 36.6 W |
Electricity |
Number of transformers | 0 |
Continuous current | |
rated value | 630 A |
at 40 °C / rated value | 598.5 A |
at 45 °C / rated value | 567 A |
at 50 °C / rated value | 535.5 A |
at 55 °C / rated value | 504 A |
at 60 °C / rated value | 472.5 A |
at 65 °C / rated value | 441 A |
at 70 °C / rated value | 409.5 A |
Let-through current / Ic / maximum permissible | |
400 V | 52 kA |
500V | 52 kA |
cut-off value I**2t,max. / 400 V | 5 400 000 A²·s |
Main circuit |
Operating voltage | |
at AC / at 50/60 Hz / rated value | 690 V |
at DC / rated value | 440 V |
Operating current / with capacitive load | |
at 400 V / maximum | 361 A |
at 500 V / maximum | 275 A |
Suitability |
Suitability for operation | System protection |
Suitability for use | |
Main switch | No |
switch disconnector | Yes |
EMERGENCY OFF switch | No |
safety switch | No |
maintenance/repair switch | No |
Product details |
Product component | |
Voltage trigger | No |
undervoltage release | No |
undervoltage release with leading contact | No |
Short circuit |
Conditional rated short-circuit current / in utilization category | |
AC-21 B / at 400 V | 110 kA |
AC-21 B / at 500 V | 110 kA |
AC-22 B / at 400 V | 110 kA |
AC-22 B / at 500 V | 110 kA |
Connections |
Arrangement of electrical connectors / for main current circuit | Screw terminal |
Type of electrical connection / for main current circuit | screw-type terminals |
Mechanical Design |
Height | 662 mm |
Width | 99.5 mm |
Depth | 195 mm |
Mounting position | vertical |
Mounting type | Flachanschluss, M 12 |
Busbar center-to-center spacing | 185 mm |
Busbar center-to-center spacing | |
40 mm | No |
50 mm | No |
60 mm | No |
100 mm | No |
185 mm | Yes |
Net weight | 6.09 kg |
Environmental conditions |
Ambient temperature | |
during operation / minimum | -25 °C |
during operation / maximum | 55 °C |