3NA3124-6 LV HRC fuse link
From SIEMENS
LV HRC fuse element, NH1, In: 80 A, gG, Un AC: 690 V, Un DC: 440 V, Front indicator, live grip lugs | ||
Model | ||
Product brand name | SENTRON | |
Product designation | LV HRC fuse link | |
Design of the product | With blade contacts | |
Design of an identification indicator | Front indicators | |
Design of the switching contact | Non-corroding, silver-plated | |
Design of the fuse link | LV HRC fuse link | |
General technical data | ||
Size of fuse system / acc. to DIN EN 60269-1 | NH1 | |
Operating class of the fuse link | gG | |
circuit-breaker / Design | 3NA3 | |
Supply voltage | ||
at AC / rated value | 690 V | |
at DC | 440 V | |
Protection class | ||
Protection class IP | IP20, with connected conductors | |
Switching capacity | ||
Switching capacity current | ||
at DC / acc. to IEC 60947-2 / rated value | 25 kA | |
acc. to IEC 60947-2 / rated value | 120 kA | |
Dissipation | ||
Power loss [W] | 6.7 W | |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 6.7 W | |
Electricity | ||
Tripping residual / rated value / derated current / at 40 Cel | 76 A | |
Current / at AC / rated value | 80 A | |
Diken-export / Let-through energy | DE_3NA_1_690_gG_80 | |
Mechanical Design | ||
Width | ||
of the enclosure | 30 mm | |
Mounting position | Any, preferably vertical | |
Net weight | 275 g | |
Environmental conditions | ||
Ambient temperature | ||
minimum | -5 °C | |
maximum | 40 °C | |
during storage | Air humidity 90% at 20 °C | |
Environmental category | -20 to +50 at 95% relative humidity |